Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: D C STEINLE INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of D C STEINLE INC in 5744 LANGES CORNERS RD, DENMARK, WI 54208 (NAICS 236220). OSHA activity number 338827835.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch D C Steinle INC for free Get an email when a new federal OSHA severe-injury report for D C Steinle INC is published. One employer, no account, unsubscribe in one click.
Establishment
D C STEINLE INC
Site address
5744 LANGES CORNERS RD
City
DENMARK
State
WI
ZIP
54208
Mailing
6907 ROCKY RUN DRIVE, RUDOLPH, WI 54475
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
4
Ownership type
Private (A)

4 citations on file for this inspection.

1926.404 B01 I

Serious Gravity 10 1 instance 3 exposed
Issued
Apr 15, 2013
Abate by
Jun 4, 2013
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites:      a) Employer did not provide ground-fault protection for employees who were utilizing electrical equipment for temporary power; 120V power supplied from permanent wiring receptacle through extension cords to hand held tools without GFCI device or Assured Equipment Grounding Conductor Program.    ABATEMENT DOCUMENTATION AND ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • · I (S) $1400
  • · Z (S) $2800

1926.404 F06

Serious Gravity 10 1 instance 3 exposed
Issued
Apr 15, 2013
Abate by
May 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:   a) On 02-12-13, an employee who was using temporary power for a hand held power drill was utilizing a 100 ft. extension cord without the ground pin.    ABATEMENT DOCUMENTATION AND ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.405 G02 III

Serious Gravity 5 4 instances 3 exposed
Issued
Apr 15, 2013
Abate by
May 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used in continuous lengths without splice or tap:   a)  On 02-12-13, employees were utilizing a 14 gauge, 100 ft. extension cord with two splices for temporary power to electric hand tools.    b)  On 02-12-13, employees were utilizing a 14 gauge, greater than 125 ft. extension cord with three splices for temporary power to electric hand tools.    c)  On 02-12-13, employees were utilizing a 16 gauge, 100 ft. extension cord with four splices for temporary power to electric hand tools.  d)  On 02-12-13, employees were utilizing a Bosch circular saw with a splice in the flexible cord.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.416 E01

Serious Gravity 5 2 instances 3 exposed
Issued
Apr 15, 2013
Abate by
May 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used:    a)  On 02-12-13, employees were utilizing a 16 gauge, 100 ft. extension cord with three frays for temporary power to hand tools.  b)  On 02-12-13, employees were utilizing a 12 gauge, 100 ft. extension cord with a worn and frayed cord at the point of connection to the female end for temporary power.  ABATEMENT CERTIFICATION REQUIRED.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338827835.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.