Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LEO PALACE GUAM CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of LEO PALACE GUAM CORPORATION in 105 GUN BEACH ROAD, TAMUNING, GU 96913 (NAICS 721110). OSHA activity number 338847031.

Watch LEO Palace Guam Corporation — free Get an email when a new federal OSHA severe-injury report for LEO Palace Guam Corporation is published. One employer, no account, unsubscribe in one click.
Site address
105 GUN BEACH ROAD
City
TAMUNING
State
GU
ZIP
96913
Mailing
105 GUN BEACH ROAD STEVE PALOMERO CHIEF ENGINEER, TAMUNING, GU 96913
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
400
Ownership type
A

6 citations on file for this inspection.

1910.37 B02

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $3000.00 · Current $1500.00 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   Prego Kitchen: On February 12, 2013, and at times prior thereto, EXIT signage had not marked the designated double exit doors.
Recent events (2)
  • — I (O) $1500
  • — Z (S) $3000

1910.219 D01

Serious Gravity 5 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $3000.00 Reduced
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):  On February 12, 2013, and at times prior thereto, belt and pulley assemblies driving exhaust fan motors were not fully enclosed in the following locations;  A. Plant Room  B. Engineering Shop
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.219 E01 I

Serious Gravity 5 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.219(e)(1)(i): Horizontal belts which had both runs seven -7 feet or less from the floor level were not guarded with a guard that extended to at least fifteen inches above the belt:  On February 12, 2013, and at times prior thereto, belt and pulley assemblies driving exhaust fan motors were not fully enclosed in the following locations;  A. Plant Room  B. Engineering Shop
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.253 B04 I

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $3000.00 Reduced
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire:  Engineering Shop: On February 12, 2013, and at times prior thereto, oxygen and acetylene compressed gas H-cylinders were stored together.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.305 B01 II

Serious Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $3000.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    On February 12, 2013, and at times prior thereto, electrical equipment was not properly guarded and live wiring was exposed in the following locations;    A. Plant Room: Electrical Panel LP-ER had five breaker openings.  B. Prego Kitchen: Electrical Panel LP-SFR had one breaker opening.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4000

1910.37 B05

Other-than-serious 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  Plant Room: On February 12, 2013, and at times prior thereto, two doors which could be mistaken for exits were not properly marked with their designation.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338847031.