Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ESOCO ORRINGTON, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ESOCO ORRINGTON, LLC in 29 INDUSTRIAL WAY, ORRINGTON, ME 04474 (NAICS 562213). OSHA activity number 338854839.

Watch Esoco Orrington, LLC — free Get an email when a new federal OSHA severe-injury report for Esoco Orrington, LLC is published. One employer, no account, unsubscribe in one click.
Site address
29 INDUSTRIAL WAY
City
ORRINGTON
State
ME
ZIP
04474
Mailing
P. O. BOX 160, ORRINGTON, ME 04474
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562213
Employees
75
Ownership type
A

8 citations on file for this inspection.

1910.212 A05

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 6, 2013
Abate by
Mar 14, 2013
Penalty
Initial $4,900 · Current $4,900
29 CFR 1910.212(a)(5):   Exposure of blades. When the periphery of the blades of a fan is less than seven (7) feet above the floor or working level, the blades shall be guarded. The guard shall have openings no larger than one-half (1/2) inch.    Fire Fighting Equipment Locker - The guard to the Taskmaster heater fan had 2" openings.
Recent events (2)
  • — I (S) $4900
  • — Z (S) $4900

1910.304 G05

Serious Gravity 10 4 instances 1 exposed
Issued
Mar 6, 2013
Abate by
Mar 13, 2013
Penalty
Initial $4,900 · Current $4,900
29 CFR 1910.304(g)(5):    Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    In the following instances, the path to ground from equipment were not permanent, continuous, and effective:    I & E Tech Room - The Sharp microwave oven had an open ground.    I & E Tech Room - The two work bench power pack strips and yellow extension cord had open grounds.
Recent events (2)
  • — I (S) $4900
  • — Z (S) $4900

1910.305 G01 IV A

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 6, 2013
Abate by
Mar 14, 2013
Penalty
Initial $1,785 · Current $1,785
29 CFR 1910.305(g)(1)(iv)(A):   Flexible cords and/or cables shall not be used as a substitute for the fixed wiring of a structure:     I & E Tech Room - The yellow extension cord was used to permanently energize the power pack strips at on the work benches.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $1785

1910.157 C01

Other-than-serious 1 instance 1 exposed
Issued
Mar 6, 2013
Abate by
Mar 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):    The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.    Rolling Stock Maintenance Shop - A 10 pound dry chemical fire extinguisher was not mounted at its location.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B01 II

Other-than-serious 1 instance 1 exposed
Issued
Mar 6, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii):     Unused openings in cabinets, boxes, and fittings shall be effectively closed.    Maintenance Department - The overhead hoist disconnect was missing a knockout plug.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.151 C

Other-than-serious 2 instances 2 exposed
Issued
Mar 6, 2013
Abate by
Apr 8, 2013
Penalty
Initial $2,380 · Current $0 Reduced
29 CFR 1910.151(c): Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.    In the following instances; suitable facilities for quick drenching or flushing of the eyes and body were not immediately available due to hazard creating incumbrances.      a)   Cooling Tower -  A 6" high dike surrounding the 500 gallon tank of sodium hypochlorite 12.5% area was an incumbrance to the emergency shower and eyewash.     b)   Water Treatment - The path from the RO system and caustic soda tank had ground incumbrances with handles sticking up from the floor cover plates.
Recent events (2)
  • — I (O) $0
  • — Z (S) $2380

1910.178 Q07

Other-than-serious 1 instance 1 exposed
Issued
Mar 6, 2013
Abate by
Mar 14, 2013
Penalty
Initial $2,975 · Current $0 Reduced
29 CFR 1910.178(q)(7):    Industrial trucks shall be examined before being placed in service, and shall not be placed in service if the examination shows any condition adversely affecting the safety of the vehicle. Such examination shall be made at least daily. Where industrial trucks are used on a round-the-clock basis, they shall be examined after each shift. Defects when found shall be immediately reported and corrected.    In the Yard - The rear floodlight on the Toyota 7785 forklift did not work.
Recent events (2)
  • — I (O) $0
  • — Z (S) $2975

1910.303 B01 VI

Other-than-serious 1 instance 2 exposed
Issued
Mar 6, 2013
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.303(b)(1)(vi):    Electrical equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees.  Arcing effects shal be taken into consideration in determining the safety of the equipment.    Maintenance Department - The plug attached to the Milwaukee 14" abrasive cut-off saw, serial #98242814, had been damaged by the arcing effects between the receptacle and ungrounded prong.
Recent events (2)
  • — I (O) $0
  • — Z (S) $4900

View Esoco Orrington, LLC's full OSHA safety record →