JOINT BASE LEWIS MCCHORD, WA ·
OSHA Inspection: ARMY DIRECTORATE OF PUBLIC WORKS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ARMY DIRECTORATE OF PUBLIC WORKS in 1010 LEGGETT AVE. BOX 339500 MAIL STOP 1AA, JOINT BASE LEWIS MCCHORD, WA 98433 (NAICS 928110). OSHA activity number 338916273.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARMY DIRECTORATE OF PUBLIC WORKS
- Site address
- 1010 LEGGETT AVE. BOX 339500 MAIL STOP 1AA
- City
- JOINT BASE LEWIS MCCHORD
- State
- WA
- ZIP
- 98433
- Mailing
- 1010 LEGGETT AVE. BOX 339500 MAIL STOP 1AA, JOINT BASE LEWIS MCCHORD, WA 98433
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 464
- Ownership type
- Federal government (D)
Citations
12 citations on file for this inspection.
1910.147 C02 II
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(2)(ii): The employer's tagout energy control program procedures did not successfully comply with 29 CFR 1910.147(c)(3) and no lockout was provided for employee protection: (a) Bldg. 9567 Two controller switches were tagged out but not locked, Fuel Pump HP-6-4 and Spare size 2. Both were capable of being locked.
Recent events (1)
- · Z (S) $0
1910.212 A01
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: (a) McChord Field Bldg. 540, LeBlond Lathe did not have chuck guard installed. (b) McChord Field Bldg. 540, Hendley Lathe did not have chuck guard installed. (c) McChord Field Bldg. 540, W.F. Wellss horizontal band saw unused portion of the blade was not guarded.
Recent events (1)
- · Z (S) $0
1910.213 H01
- Issued
- Apr 15, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.213(h)(1): The sides of the lower exposed portion of the blade of radial saw(s) were not guarded to the full diameter of the blade by a device that automatically adjusted itself to the thickness of the stock and remained in contact with the material: (a) Lewis Main Structural Carpenter Shop, Dewalt 18 inch radial arm saw lower blade guard was secured in the up out or the way position. (b) McChord Field Structural Carpenter Shop bldg. 540, Dewalt radial arm saw did not have a lower blade guard.
Recent events (1)
- · Z (S) $0
1910.215 A04
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): Grinding machinery was not used with work rest(s) to support offhand grinding work: (a) Bldg. 3292 Dayton 8 inch grinder Model 42909c was not equipped with a tool rest to support offhand grinding. (b) Bldg. 1206 Dayton 8 inch grinder Model 42909c tool rest was approximately 1 inch from the grinding wheel
Recent events (1)
- · Z (S) $0
1910.215 B09
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: (a) Bldg. 9576, Dayton Bench grinder 2z4260 did not have a tongue guard and the end safety peripheral member member exceeded one fourth inch. (b) Bldg. 2045, Milwaukee LIN 879616 Ser. 95-211KWG tongue guards exceeded one fourth inch. (c) Bldg. 1206, Dayton 4z9096 8 inch grinder tongue guard was approximately one half inch above grinding wheel. (d) Structural carpenter shop Dayton 2lkr6 8 inch grinder did not have a tongue guard and the end safety peripheral member exceeded one fourth inch. (e) Bldg 540 McChord Field Baylor 1215 pedestal grinder tongue guard was approximately three quarter of an inch above grinding wheel. (corrected during the inspection)
Recent events (1)
- · Z (S) $0
1910.219 D01
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): (a) Inside electric shop bldg. 2045 Atlas drill press drive pulleys were not guarded.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Bldg. 33292 electrical junction box did not have cover.
Recent events (1)
- · Z (S) $0
1910.157 C01
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: (a) Forestry bldg. 1206, four portable fire extinguishers were placed on the floor instead of mounted for easy access by employees.
Recent events (1)
- · Z (O) $0
1910.212 B
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving: (a) Bldg. 1206 Jet drill press MJDP-20MF SN 2050121. (b) Bldg. 1206 Dayton Pedestal grinder. (c) Bldg. 2045 Dayton 20 inch drill press LIN 62920D. (c) Bldg. 2045 Atlas drill press. (d) Structural carpenter/metal shop Lewis Main Wilt 5816 drill press SN 31451. (c) Bldg 540 McChord Field Delta drill press Model 11-990 SN 014724W1074.
Recent events (1)
- · Z (O) $0
1910.303 G01
- Issued
- Apr 15, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: (a) Lewis Main Structural welding shop, tool boxes blocked electrical panel.
Recent events (1)
- · Z (O) $0
1910.305 G01 IV A
- Issued
- Apr 15, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Lewis Main Structural welding shop, Extension cord was wire tied to conduit across the shop to power a light on Piranha metal worker.
Recent events (1)
- · Z (O) $0
1910.305 G02 III
- Issued
- Apr 15, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) McChord Field Bldg. 540 overhead reel type extension cord strain relief was damaged at the outlet end.
Recent events (1)
- · Z (O) $0
More inspections at Army Directorate of Public Works
View Army Directorate of Public Works's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338916273.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.