OSHA Inspection: MILITARY DISTRIBUTORS OF VIRGINIA, INC..

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MILITARY DISTRIBUTORS OF VIRGINIA, INC.. in 4150 W BLOUNT STREET, PENSACOLA, FL 32505 (NAICS 424410). OSHA activity number 338917081.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Military Distributors of Virginia, INC.. — free Get an email when a new federal OSHA severe-injury report for Military Distributors of Virginia, INC.. is published. One employer, no account, unsubscribe in one click.
Site address
4150 W BLOUNT STREET
City
PENSACOLA
State
FL
ZIP
32505
Mailing
4150 W BLOUNT STREET, PENSACOLA, FL 32505
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424410
Employees
70
Ownership type
A

3 citations on file for this inspection.

1910.303 G01

Other-than-serious 1 instance 2 exposed
Issued
Mar 18, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1):     Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    a.  On or about February 25, 2013, on the north side, 208 and 480 volt panel boxes were blocked by two industrial battery charging stations.
Recent events (1)
  • — Z (O) $0

1910.303 G02 I

Other-than-serious 1 instance 1 exposed
Issued
Mar 18, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidentalcontact by use of approved cabinets or other forms of approved enclosures or by any of the following means:    a.  On or about February 25, 2013, outside in the pump room next to the 200,000K gallon water tank, a 115 volt fire pump controller panel boxes had wiring protruding from an open enclosure box.
Recent events (1)
  • — Z (O) $0

1910.305 G01 IV B

Other-than-serious 1 instance 2 exposed
Issued
Mar 18, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B):     Where run through holes in walls, ceilings, or floors:    a.  On or about February 25, 2013, inside the maintenance cage, a flexible power cord ran through a hole in the wall.
Recent events (1)