Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WALSH ELECTRICAL, INCORPORATED

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of WALSH ELECTRICAL, INCORPORATED in 235 MONTAGE MOUNTAIN ROAD, MOOSIC, PA 18507 (NAICS 238210). OSHA activity number 338918626.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Walsh Electrical, Incorporated — free Get an email when a new federal OSHA severe-injury report for Walsh Electrical, Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
235 MONTAGE MOUNTAIN ROAD
City
MOOSIC
State
PA
ZIP
18507
Mailing
916 OAK STREET, SCRANTON, PA 18508
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
32
Ownership type
A

2 citations on file for this inspection.

1926.416 A01

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Mar 6, 2013
Abate by
Mar 12, 2013
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1926.416(a)(1):   Employer permitted employees to work in proximity to electric power circuits without the employees being protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.  a) "3rd Base" Switchgear Room, PNC Stadium, 235 Montage Mountain Road, Moosic, PA: An employee attaching conductors to the DP-MC-C2-1 circuit breaker located in the "3rd Base" switchgear received an electric shock. The electric power circuit was energized by the "1st Base" switchgear that was "backfeeding" the circuit through the DP-MC-C2-1 panel, on or about February 21, 2013.  In accordance with 29 CFR 1903.19(c) and (d), abatement certification and documentation is required for this violation.
Recent events (3)
  • — F (S) $0
  • — C (S) $4900
  • — Z (S) $4900

1926.417 B

Other-than-serious 1 instance 4 exposed
Issued
Mar 6, 2013
Abate by
Mar 12, 2013
Penalty
Initial $4,900 · Current $4,900
29 CFR 1926.417(b):   Equipment or circuits that were deenergized were not rendered inoperative and did not have tags attached at all points where such equipment or circuits could be energized.  a) "3rd Base" Switchgear Room, PNC Stadium, 235 Montage Mountain Road, Moosic, PA: The DP-MC-C2-1 Electrical Panel "Main" circuit breaker was deenergized but was not rendered inoperative or tagged. Persons unknown reenergized the DP-MC-C2-1 Electrical Panel "Main" circuit breaker and an employee attaching conductors from the DP-MC-C2-1 Electrical Panel to the DP-MC-C2-1 circuit breaker located in the "3rd Base" switchgear received an electric shock, on or about February 21, 2013.  In accordance with 29 CFR 1903.19(c) and (d), abatement certification and documentation is required for this violation.
Recent events (3)
  • — F (O) $4900
  • — C (S) $4900
  • — Z (S) $4900

View Walsh Electrical, Incorporated's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338918626.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.