PHILADELPHIA, PA —
OSHA Inspection: LARRY C. MCCRAE, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of LARRY C. MCCRAE, INC. in 1800 WARNOCK STREET, PHILADELPHIA, PA 19140 (NAICS 238210). OSHA activity number 338919822.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LARRY C. MCCRAE, INC.
- Site address
- 1800 WARNOCK STREET
- City
- PHILADELPHIA
- State
- PA
- ZIP
- 19140
- Mailing
- 3333 W. HUNTING PARK AVENUE, PHILADELPHIA, PA 19132
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 50
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.403 B02
- Issued
- Mar 12, 2013
- Abate by
- Mar 29, 2013
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: (a) 1800 Warnock Street, Electrical service panel - On or about 2/23/2013, employees who were performing electrical work were exposed to electrical shock from Romex electrical cable listed for use in normally dry areas which was used in an outdoor and wet location for branch circuit wiring from the service panel to the site. \ Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $2100
1926.404 C01 II D
- Issued
- Mar 12, 2013
- Abate by
- Mar 22, 2013
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1926.404(c)(1)(ii)(D): Open conductors for branch circuit, feeder, and service conductors rated 600 volts, nominal, or less and run outdoors did not conform to the minimum clearance of 18 feet over public streets, alleys, roads, and driveways: (a) 1800 Warnock Street, Electrical service entrance line over Warnock Street - On or about 2/26/2013, employees performing electrical work were exposed to hazards of vehicle traffic interfering the service electrical line which was not the required 18 feet above the street. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $2800
1926.404 F07 II
- Issued
- Mar 12, 2013
- Abate by
- Mar 18, 2013
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1926.404(f)(7)(ii): Metal enclosures for service equipment were not grounded: (a) 1800 Warnock Street, Electrical service panel - On or about 2/26/2013, employees performing electrical work were exposed to electrical hazards from an electrical service panel that was not grounded. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $2800
1926.405 B01
- Issued
- Mar 12, 2013
- Abate by
- Mar 22, 2013
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: (a) 1800 Warnock Street, Electrical service panel box - On or about 2/26/2013, employees performing electrical work at the site were exposed to electrical hazards from an unused opening in the electrical service panel that was not effectively closed. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $2100
1926.405 E01
- Issued
- Mar 12, 2013
- Abate by
- Mar 22, 2013
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1926.405(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosures: (a) 1800 Warnock Street, Electrical service panel box - On or about 2/26/2013, employees performing electrical work at the site were exposed to electrical hazards from an electrical service panel that was installed outdoors in the weather, not protected from water or moisture intrusion and was not rated or listed for use in damp or wet locations. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $2800
More inspections at Larry C. Mccrae, INC.
View Larry C. Mccrae, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338919822.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.