OSHA Inspection: LARRY C. MCCRAE, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of LARRY C. MCCRAE, INC. in 1800 WARNOCK STREET, PHILADELPHIA, PA 19140 (NAICS 238210). OSHA activity number 338919822.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Larry C. Mccrae, INC. — free Get an email when a new federal OSHA severe-injury report for Larry C. Mccrae, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1800 WARNOCK STREET
City
PHILADELPHIA
State
PA
ZIP
19140
Mailing
3333 W. HUNTING PARK AVENUE, PHILADELPHIA, PA 19132
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
50
Ownership type
A

5 citations on file for this inspection.

1926.403 B02

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 12, 2013
Abate by
Mar 29, 2013
Penalty
Initial $2,100 · Current $2,100
29 CFR 1926.403(b)(2):     Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    (a) 1800 Warnock Street, Electrical service panel - On or about 2/23/2013, employees who were performing electrical work were exposed to electrical shock from Romex electrical cable listed for use in normally dry areas which was used in an outdoor and wet location for branch circuit wiring from the service panel to the site.   \  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $2100

1926.404 C01 II D

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 12, 2013
Abate by
Mar 22, 2013
Penalty
Initial $2,800 · Current $2,800
29 CFR 1926.404(c)(1)(ii)(D):     Open conductors for branch circuit, feeder, and service conductors rated 600 volts, nominal, or less and run outdoors did not conform to the minimum clearance of 18 feet over public streets, alleys, roads, and driveways:    (a) 1800 Warnock Street, Electrical service entrance line over Warnock Street - On or about 2/26/2013, employees performing electrical work were exposed to hazards of vehicle traffic interfering the service electrical line which was not the required 18 feet above the street.    Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $2800

1926.404 F07 II

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 12, 2013
Abate by
Mar 18, 2013
Penalty
Initial $2,800 · Current $2,800
29 CFR 1926.404(f)(7)(ii):     Metal enclosures for service equipment were not grounded:    (a) 1800 Warnock Street, Electrical service panel - On or about 2/26/2013, employees performing electrical work were exposed to electrical hazards from an electrical service panel that was not grounded.    Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $2800

1926.405 B01

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 12, 2013
Abate by
Mar 22, 2013
Penalty
Initial $2,100 · Current $2,100
29 CFR 1926.405(b)(1):     Unused openings in cabinets, boxes, and fittings were not effectively closed:    (a) 1800 Warnock Street, Electrical service panel box - On or about 2/26/2013, employees performing electrical work at the site were exposed to electrical hazards from an unused opening in the electrical service panel that was not effectively closed.    Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (1)
  • — Z (S) $2100

1926.405 E01

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 12, 2013
Abate by
Mar 22, 2013
Penalty
Initial $2,800 · Current $2,800
29 CFR 1926.405(e)(1):     Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosures:    (a) 1800 Warnock Street, Electrical service panel box - On or about 2/26/2013, employees performing electrical work at the site were exposed to electrical hazards from an electrical service panel that was installed outdoors in the weather, not protected from water or moisture intrusion and was not rated or listed for use in damp or wet locations.    Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.