NORWICH, NY —
OSHA Inspection: NORWICH BEVERAGE CORP.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NORWICH BEVERAGE CORP. in 4848 STATE HIGHWAY 23, NORWICH, NY 13815 (NAICS 424810). OSHA activity number 338919871.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NORWICH BEVERAGE CORP.
- Site address
- 4848 STATE HIGHWAY 23
- City
- NORWICH
- State
- NY
- ZIP
- 13815
- Mailing
- P.O. BOX 369, NORWICH, NY 13815
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424810
- Employees
- 25
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.151 C
- Issued
- Mar 21, 2013
- Abate by
- Apr 25, 2013
- Penalty
- Initial $1,020 · Current $714 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) Loading Dock, on or about 2/26/13: No eye wash was providing for employees when servicing batteries for the forklifts. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $714
- — Z (S) $1020
1910.305 G01 IV A
- Issued
- Mar 21, 2013
- Abate by
- Apr 25, 2013
- Penalty
- Initial $1,020 · Current $714 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Receiving Area, on or about 2/26/13: Two extension cords providing current to the engine block heaters on the delivery trucks were run under the dock doors to the outside and were being used as permanent wiring. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $714
- — Z (S) $1020
1910.334 A02 I
- Issued
- Mar 21, 2013
- Abate by
- Apr 2, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): a) Receiving Area, on or about 2/26/13: An extension cord used to provide power to the engine block heaters on delivery trucks had cuts to the outer jacket and had not been removed from service. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.22 B01
- Issued
- Mar 21, 2013
- Abate by
- Apr 2, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(b)(1): Aisles and passageways were not kept clear and in good repair: a) Loading dock, on or about 2/26/13: A fixed stairway with six risers was not kept in good repair in that the steps were cracked, sections of the steps were missing and leading edges were worn. Abatement certification must be submitted for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.37 A03
- Issued
- Mar 21, 2013
- Abate by
- Apr 2, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit routes were not free and unobstructed. Materials or equipment were placed, either permanently or temporarily, within the exit route: a) Loading dock, on or about 2/26/13: Exit door was blocked by a pallet, two bags of Oil Dri, a wooden board and a shop vac. Abatement certification must be submitted for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Norwich Beverage Corp.
View Norwich Beverage Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 424810)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338919871.