Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: TUNKHANNOCK MANOR

Special Programs inspection · Health discipline

On , OSHA opened a special Programs health inspection of TUNKHANNOCK MANOR in 50 WEST TIOGA STREET, TUNKHANNOCK, PA 18657 (NAICS 623312). OSHA activity number 338924350.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tunkhannock Manor for free Get an email when a new federal OSHA severe-injury report for Tunkhannock Manor is published. One employer, no account, unsubscribe in one click.
Establishment
TUNKHANNOCK MANOR
Site address
50 WEST TIOGA STREET
City
TUNKHANNOCK
State
PA
ZIP
18657
Mailing
50 WEST TIOGA STREET, TUNKHANNOCK, PA 18657
Inspection type
Special Programs (K)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623312
Employees
37
Ownership type
A

2 citations on file for this inspection.

1910.305 J02 IV

Serious Gravity 1 1 instance 5 exposed
Issued
Mar 6, 2013
Abate by
Apr 22, 2013
Penalty
Initial $2,550 · Current $1,913 Reduced
29 CFR 1910.305(j)(2)(iv):     A receptacle installed in a wet or damp location was not suitable for the location:    a) Dietary Department, 120 volt outlets used to power portable kitchen appliances, including coffee makers, hotplates, a meat slicer, microwave oven, and toasters, were not equipped with ground fault circuit interruption (GFCI), February 28, 2013    "ABATEMENT CERTIFICATION REQUIRED"
Recent events (2)
  • · I (S) $1912.5
  • · Z (S) $2550

1910.305 J02 II

Serious Gravity 5 1 instance 5 exposed
Issued
Mar 6, 2013
Abate by
Apr 1, 2013
Penalty
Initial $4,250 · Current $3,188 Reduced
29 CFR 1910.305(j)(2)(ii):     Receptacles, cord connectors, and attachment plugs were not constructed so that a receptacle or cord connector would not accept an attachment plug with a different voltage or current rating than that for which the device was intended:    a) Dietary Department, a female wall mounted receptacle was powered through a 220 volt single phase circuit.  The outlet's configuration was not constructed to prevent the insertion of common 120 volt plugs and cordsets of NEMA 1-15R, 5-15R and 5-20R configuration, February 28, 2013.    "ABATEMENT CERTIFICATION REQUIRED"
Recent events (2)
  • · I (S) $3187.5
  • · Z (S) $4250

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338924350.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.