OSHA Inspection: U.S. CUSTOMS AND BORDER PROTECTION-CARIBBEAN AIR + MARINE BRANCH

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. CUSTOMS AND BORDER PROTECTION-CARIBBEAN AIR + MARINE BRANCH in 575A BROMON DR, AGUADILLA, PR 00604 (NAICS 928110). OSHA activity number 338939556.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Customs and Border Protection-Caribbean AIR + Marine Branch for free Get an email when a new federal OSHA severe-injury report for U.S. Customs and Border Protection-Caribbean AIR + Marine Branch is published. One employer, no account, unsubscribe in one click.
Site address
575A BROMON DR
City
AGUADILLA
State
PR
ZIP
00604
Mailing
P.O. BOX 250429, AGUADILLA, PR 00604
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
100
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.22 D01

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate:  On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in the hangar supply room area, an elevated floor used as storage was not marked with the floor load rating capacity.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.37 A03

Serious Gravity 5 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit routes must be free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route. The exit access must not go through a room that can be locked, such as a bathroom, to reach an exit or exit discharge, nor may it lead into a dead-end corridor. Stairs or a ramp must be provided where the exit route is not substantially level:   On or about 03/04/13, at 575 a Bromon Drive, Aguadilla, PR, in the gym area, the exit door was blocked with exercise equipment.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS NOT REQUIRED FOR THIS VIOLATION, VIOLATION WAS CORRECTED DURING INSPECTION.
Recent events (1)
  • · Z (S) $0

1910.37 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit must be clearly visible and marked by a sign reading "Exit":   On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in the gym area, the "EXIT" sign of a designated exit was completely blocked by tv equipment.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 1 2 instances 3 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:   a) On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in the electrical room area, two relocatable power taps were not connected to a permanently installed branch circuit receptacle.   b) On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in Trailer #6 kitchen area, a ground-fault circuit interrupter was not installed in all 125-volt, single phase, 15-and 20-ampere receptacles installed within 6 feet or 1.8 meters of the outside edge of a sink.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment:  On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in Trailer #8B area, an electrical service panel was not readily accessible.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 1 2 instances 3 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed:  a) On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in tool box room area, a circuit breaker panel had unused openings not covered.  b) On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in the hangar area, circuit breaker panel LPA4 had unused openings not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Sep 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:  On or about 03/04/13, at 575 A Bromon Drive, Aguadilla, PR, in trailer #6 kitchen area, a flexible cord was used in lieu of permanent wiring to service a wall mounted receptacle.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338939556.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.