GREENWOOD, MS —
OSHA Inspection: VIKING RANGE CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VIKING RANGE CORPORATION in 5601 VIKING ROAD, GREENWOOD, MS 38930 (NAICS 335228). OSHA activity number 338947625.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VIKING RANGE CORPORATION
- Site address
- 5601 VIKING ROAD
- City
- GREENWOOD
- State
- MS
- ZIP
- 38930
- Mailing
- 5601 VIKING ROAD, GREENWOOD, MS 38930
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335228
- Employees
- 718
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C04 II C
- Issued
- May 24, 2013
- Abate by
- Jun 13, 2013
- Penalty
- Initial $3,600 · Current $2,160 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(C): Specific procedural steps for the placement, removal and transfer of lockout devices or tagout devices and the responsibility for them. (a) Viking Range, East Plant - On or about March 26, 2013 specific procedures for controlling hazardous energy when performing maintenance on equipment were not developed and implemented.
Recent events (2)
- — I (S) $2160
- — Z (S) $3600
1910.212 A03 II
- Issued
- May 24, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $3,600 · Current $2,160 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): The point of operation of machines whose operation exposes an employee to injury, shall be guarded. The guarding device shall be in conformity with any appropriate standards therefor, or, in the absence of applicable specific standards, shall be so designed and constructed as to prevent the operator from having any part of his body in the danger zone during the operating cycle. (a) Canopy Department and Welding Department - on or about March 7, 2013, 3 stroke belt sanders located in the Canopy Departmentt and 2 stroke belt Sanders located in the Welding Department did not have idler wheel covers (guards).
Recent events (2)
- — I (S) $2160
- — Z (S) $3600
1910.303 F02
- Issued
- May 24, 2013
- Abate by
- May 31, 2013
- Penalty
- Initial $2,700 · Current $1,620 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. (a) QC Test Panel - On or about March 7, 2013, the circuit breakers in electrical panel 31 were not labeled to indicate what each breaker controls.
Recent events (2)
- — I (S) $1620
- — Z (S) $2700
1910.304 G05
- Issued
- May 24, 2013
- Abate by
- May 24, 2013
- Penalty
- Initial $3,060 · Current $1,836 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. (a) Welding Department - On or about March 7, 2013, the large commercial fan was not grounded. The power cord did not have a grounding prong.
Recent events (2)
- — I (S) $1836
- — Z (S) $3060
1910.305 B01 I
- Issued
- May 24, 2013
- Abate by
- May 24, 2013
- Penalty
- Initial $3,060 · Current $1,836 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. (a) Canopy Department - On or about March 7, 2013, the power cord for the Kuhlmeyer belt sander was not protected from abrasion and the opening where the power cord entered the electric motor was not closed.
Recent events (2)
- — I (S) $1836
- — Z (S) $3060
1910.305 B01 II
- Issued
- May 24, 2013
- Abate by
- May 24, 2013
- Penalty
- Initial $3,060 · Current $1,836 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. (a) Maintenance Department - On or about March 6, 2013, circuit breaker number 28 was removed from the circuit breaker panel and the opening was not covered. The circuit breaker panel is located next to the roll-up door.
Recent events (2)
- — I (S) $1836
- — Z (S) $3060
1910.305 B01 II
- Issued
- May 24, 2013
- Abate by
- May 24, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. (a). Model Department - On or about March 7, 2013, a knockout plug was missing from the electrical receptacle for the sander and punch press. The receptacle had an unused opening.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- May 24, 2013
- Abate by
- Jun 13, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. (a). Welding Department - On or about March 6, 2013, the throw switch for the Millermatic 200 welder was blocked by empty compressed gas cylinders.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Viking Range Corporation
View Viking Range Corporation's full OSHA safety record →
More inspections in this industry (NAICS 335228)
More inspections in MS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338947625.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.