Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SAN VAL INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SAN VAL INC. in 895 FRISCO ST., STEELVILLE, MO 65565 (NAICS 323121). OSHA activity number 338953359.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch SAN VAL INC. — free Get an email when a new federal OSHA severe-injury report for SAN VAL INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SAN VAL INC.
Site address
895 FRISCO ST.
City
STEELVILLE
State
MO
ZIP
65565
Mailing
895 FRISCO ST., STEELVILLE, MO 65565
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323121
Employees
32
Ownership type
A

6 citations on file for this inspection.

1910.147 D04 I

Serious Gravity 1 2 instances 4 exposed
Issued
Mar 21, 2013
Abate by
May 7, 2013
Penalty
Initial $2,100 · Current $1,470 Reduced
29 CFR 1910.147(d)(4)(i):     Lockout or tagout devices were not affixed to each energy isolating device by authorized employees:    a. Equipment was not locked out when a cover/guard was removed from the laminator for cleaning.    b. Equipment was not locked out (or unplugged) when rollers were removed for cleaning from the caser machine.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $1470
  • — Z (S) $2100

1910.303 B02

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
Dec 11, 2013
Penalty
Initial $2,100 · Current $1,470 Reduced
29 CFR 1910.303(b)(2):     Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a. Relocatable power taps (power strips) were not used according to their listed use; a power strip was plugged into an extension cord which was plugged into another power strip in order to power glue machine.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $1470
  • — Z (S) $2100

1910.303 G02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 21, 2013
Abate by
May 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    a. At the glue machine, the power cord was missing a ground pin and found with live voltage on the motor case and machine covers.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 21, 2013
Abate by
May 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5):     The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    a. At the glue machine, the power cord was missing a ground pin and found with live voltage on the motor case and machine covers.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
May 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii):     Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:    a. Flexible power cords were damaged (no strain relief) on the forklift battery chargers.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 A02

Other-than-serious 1 instance 1 exposed
Issued
Mar 21, 2013
Abate by
May 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(a)(2):     Grounded conductors were attached to terminals or leads so as to reverse designated polarity:    a. At the laminator table, a 110 V outlet was used with reverse polarity, to power equipment.    Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View SAN VAL INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338953359.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.