BERLIN, NH ·
OSHA Inspection: VAILLANCOURT ELECTRIC SERVICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VAILLANCOURT ELECTRIC SERVICE in COMMUNITY STREET, BERLIN, NH 03570 (NAICS 238210). OSHA activity number 338954092.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VAILLANCOURT ELECTRIC SERVICE
- Site address
- COMMUNITY STREET
- City
- BERLIN
- State
- NH
- ZIP
- 03570
- Mailing
- 244 GLEN AVE, BERLIN, NH 03570
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 20
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1926.95 A
- Issued
- Sep 10, 2013
- Abate by
- Sep 16, 2013
- Penalty
- Initial $2,800 · Current $0 Reduced
General-duty citation text
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided, used, and maintained in a sanitary and reliable condition: (a) Transformer Yard Employees were exposed to electrical shock hazards while working on live 480 volt panel without any personal protective equipment.
Recent events (2)
- · I (S) $0
- · Z (S) $2800
1926.416 A01
- Issued
- Sep 10, 2013
- Abate by
- Sep 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: (a) Transformer Yard Employees were exposed to an electrical shock hazard while working on unguarded electrical equipment.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1926.403 H
- Issued
- Sep 10, 2013
- Penalty
- Initial $2,800 · Current $0 Reduced
General-duty citation text
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident:ALLEGED VIOLATION DESCRIPTION (A.V.D.): Reclaimer Tunnel The circuit breakers in the electrical service panel were not labeled as to their use.
Recent events (2)
- · I (S) $0
- · Z (S) $2800
1926.405 A02 II C
- Issued
- Sep 10, 2013
- Penalty
- Initial $1,200 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(C): Receptacles for uses other than temporary lighting were installed on branch circuits which supplied temporary lighting: (a) Site - Employees were not protected from slips, trips, and falls when the temporary lighting throughout the site was connected to the same GFCI outlets that were being used to power hand tools. (b) Re-claimer Tunnel The temporary lights were not installed on dedicated circuits.
Recent events (2)
- · I (S) $0
- · Z (S) $1200
1926.405 B01
- Issued
- Sep 10, 2013
- Penalty
- Initial $2,000 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(b)(1): Openings in boxes, cabinets, and fittings through which conductors entered were not effectively closed: (a) Boiler Room Building, 1st Floor - Employees were not protected from electrical shocks and burns when the cabinet for the temporary electric panel contained unused openings that were not effectively closed. (b) Re-claimer Tunnel The main electrical service panel had unused openings.
Recent events (2)
- · I (S) $0
- · Z (S) $2000
1926.405 G02 IV
- Issued
- Sep 10, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: a. Boiler Room Building, 1st Floor - Employees were not protected from electrical shocks and burns when flexible cords exiting the temporary electric cabinet were not provided with strain relief resulting in two cords having exposed live wiring.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1926.405 E01
- Issued
- Sep 10, 2013
- Penalty
- Initial $2,800 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(e)(1): Panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosures: a. Boiler Room Building - Employees were not protected from electrical shocks and burns when the electric panel for the temporary power was not weatherproof and was located beneath a floor drain which poured water directly onto the cabinet.
Recent events (2)
- · I (S) $0
- · Z (S) $2800
More inspections in this industry (NAICS 238210)
More inspections in NH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338954092.