SCOTT CITY, MO —
OSHA Inspection: HAVCO WOOD PRODUCTS LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of HAVCO WOOD PRODUCTS LLC in 3200 E. OUTER RD., SCOTT CITY, MO 63780 (NAICS 321918). OSHA activity number 338967599.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HAVCO WOOD PRODUCTS LLC
- Site address
- 3200 E. OUTER RD.
- City
- SCOTT CITY
- State
- MO
- ZIP
- 63780
- Mailing
- P.O. BOX 1342, CAPE GIRARDEAU, MO 63702
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321918
- Employees
- 306
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.23 C01
- Issued
- Apr 5, 2013
- Abate by
- Jun 13, 2013
- Penalty
- Initial $2,250 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards: a. In the loading area of the processing building, where product was loaded onto flatbed trucks without railing or other fall protection (truck beds 55-57 inches on two trucks in the building at the time of the inspection), employees loading and securing the load while standing on the truck bed and at somewhat higher heights when standing on the loaded product, were exposed to a fall. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
- — I (S) $1575
- — Z (S) $2250
1910.169 B03 IV
- Issued
- Apr 5, 2013
- Abate by
- Jun 13, 2013
- Penalty
- Initial $2,250 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.169(b)(3)(iv): Safety valve(s) on compressed air receiver(s) were not tested at frequently regular intervals to determine if they were in good operating condition: a. Where 5 gal air tanks were used for maintenance in the truck building, safety relief valves were not regularly tested. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
- — I (S) $1575
- — Z (S) $2250
1910.304 G05
- Issued
- Apr 5, 2013
- Abate by
- Jun 13, 2013
- Penalty
- Initial $2,250 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a. Examples existed of ground pins missing from equipment, such as, but not limited to, 110 V cooling fans with flexible power cords. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
- — I (S) $1575
- — Z (S) $2250
1910.147 C04 II
- Issued
- Apr 5, 2013
- Abate by
- Dec 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D)(h): a. Specific lockout procedures for each type of equipment where specific procedures were required, were not developed for all equipment, such as, but not limited to, the Putty Machine, Rex Machine, Plug Cutter, and Chop/Defect Saws (note: lockout was being performed and training had been provided). Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Havco Wood Products LLC
View Havco Wood Products LLC's full OSHA safety record →
More inspections in this industry (NAICS 321918)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338967599.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.