Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: QUALAWASH HOLDINGS, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of QUALAWASH HOLDINGS, LLC in 6551 GRANT AVE., CLEVELAND, OH 44105 (NAICS 562998). OSHA activity number 338969397.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Qualawash Holdings, LLC for free Get an email when a new federal OSHA severe-injury report for Qualawash Holdings, LLC is published. One employer, no account, unsubscribe in one click.
Site address
6551 GRANT AVE.
City
CLEVELAND
State
OH
ZIP
44105
Mailing
6551 GRANT AVE., CLEVELAND, OH 44105
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562998
Employees
43
Ownership type
Private (A)

7 citations on file for this inspection.

1910.106 E02 II A

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 25, 2013
Abate by
Aug 13, 2013
Penalty
Initial $4,250 · Current $3,000 Reduced
29 CFR 1910.106(e)(2)(ii)(a): Except as provided in 1910.106(e)(2)(ii)(b) and (c) all storage did not comply with 1910.106(d)(3) or (4):        The dock staging and/or storage area, which contained category 3 flammable liquids, did not comply with the provisions of 1910.106 (d) (4) for the design and construction of an inside storage room.
Recent events (3)
  • · F (S) $3000
  • · C (S) $4250
  • · Z (S) $4250

1910.106 E02 II B 2

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 25, 2013
Abate by
Aug 13, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons:          On or before 03/08/2013, there was greater than 120 gallons of Category 3 flammable liquids outside of a storage room or cabinet.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

1910.106 E07 I A

Serious Gravity 5 1 instance 43 exposed
Issued
Jul 25, 2013
Abate by
Aug 13, 2013
Penalty
Initial $5,100 · Current $3,400 Reduced
29 CFR 1910.106(e)(7)(i)(a): All electrical wiring and equipment was not installed according to the requirements of Subpart S of this part:           General building electrical wiring, located in the Poly room, which contained Category 3 flammable liquids, was not installed in accordance with the requirements for Class 1 Division 2 chemicals.
Recent events (3)
  • · F (S) $3400
  • · C (S) $5100
  • · Z (S) $5100

1910.307 C

Serious Gravity 5 2 instances 43 exposed
Issued
Jul 25, 2013
Abate by
Aug 13, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:             General building wiring, to include the 480 volt electrical distribution boxes, located in the Poly room where Category 3 flammable liquids were stored, were not installed in accordance with the requirements for Class 1, Division 2 chemicals.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 5 2 instances 43 exposed
Issued
Jul 25, 2013
Penalty
Initial $3,400 · Current $3,400
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:           Electrical junction boxes that were damaged and/or the unused openings was not effectively closed, remained in service. The electrical junction boxes include, but or not limited to:      a. An electrical junction box, located on a pillar, in the walkway leading to the PPG department/area;      b. An electrical junction box, located on a pillar in the shipping and receiving department.
Recent events (3)
  • · F (S) $3400
  • · C (S) $3400
  • · Z (S) $3400

1910.305 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 25, 2013
Penalty
Initial $3,400 · Current $0 Reduced
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panel board enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:           The protective covering of a junction box, located on the wash line of the facility, was missing and did not prevent moisture from accumulating within the enclosure.
Recent events (3)
  • · F (S) $0
  • · C (S) $3400
  • · Z (S) $3400

1910.157 C04

Deleted Other-than-serious 2 instances 43 exposed
Issued
Jul 25, 2013
Abate by
Aug 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition:   On or about 03/08/2013, two of the company's portable fire extinguishers were missing the safety pin. The portable fire extinguishers include, but are not limited to the following:    a. The Amerex (10 lbs.), ABC rechargeable fire extinguisher, located on a pillar, in the wash bay area;    b. The ABC rechargeable fire extinguisher, located on a fork truck, in the shipping and receiving department.
Recent events (3)
  • · F (O) $0
  • · C (O) $0
  • · Z (O) $0

View Qualawash Holdings, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338969397.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.