CLEVELAND, OH ·
OSHA Inspection: QUALAWASH HOLDINGS, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of QUALAWASH HOLDINGS, LLC in 6551 GRANT AVE., CLEVELAND, OH 44105 (NAICS 562998). OSHA activity number 338969397.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- QUALAWASH HOLDINGS, LLC
- Site address
- 6551 GRANT AVE.
- City
- CLEVELAND
- State
- OH
- ZIP
- 44105
- Mailing
- 6551 GRANT AVE., CLEVELAND, OH 44105
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562998
- Employees
- 43
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1910.106 E02 II A
- Issued
- Jul 25, 2013
- Abate by
- Aug 13, 2013
- Penalty
- Initial $4,250 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.106(e)(2)(ii)(a): Except as provided in 1910.106(e)(2)(ii)(b) and (c) all storage did not comply with 1910.106(d)(3) or (4): The dock staging and/or storage area, which contained category 3 flammable liquids, did not comply with the provisions of 1910.106 (d) (4) for the design and construction of an inside storage room.
Recent events (3)
- · F (S) $3000
- · C (S) $4250
- · Z (S) $4250
1910.106 E02 II B 2
- Issued
- Jul 25, 2013
- Abate by
- Aug 13, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(e)(2)(ii)(b)(2): The quantity of Category 2, 3 or 4 flammable liquid located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 120 gallons: On or before 03/08/2013, there was greater than 120 gallons of Category 3 flammable liquids outside of a storage room or cabinet.
Recent events (3)
- · F (S) $0
- · C (S) $0
- · Z (S) $0
1910.106 E07 I A
- Issued
- Jul 25, 2013
- Abate by
- Aug 13, 2013
- Penalty
- Initial $5,100 · Current $3,400 Reduced
General-duty citation text
29 CFR 1910.106(e)(7)(i)(a): All electrical wiring and equipment was not installed according to the requirements of Subpart S of this part: General building electrical wiring, located in the Poly room, which contained Category 3 flammable liquids, was not installed in accordance with the requirements for Class 1 Division 2 chemicals.
Recent events (3)
- · F (S) $3400
- · C (S) $5100
- · Z (S) $5100
1910.307 C
- Issued
- Jul 25, 2013
- Abate by
- Aug 13, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: General building wiring, to include the 480 volt electrical distribution boxes, located in the Poly room where Category 3 flammable liquids were stored, were not installed in accordance with the requirements for Class 1, Division 2 chemicals.
Recent events (3)
- · F (S) $0
- · C (S) $0
- · Z (S) $0
1910.305 B01 II
- Issued
- Jul 25, 2013
- Penalty
- Initial $3,400 · Current $3,400
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Electrical junction boxes that were damaged and/or the unused openings was not effectively closed, remained in service. The electrical junction boxes include, but or not limited to: a. An electrical junction box, located on a pillar, in the walkway leading to the PPG department/area; b. An electrical junction box, located on a pillar in the shipping and receiving department.
Recent events (3)
- · F (S) $3400
- · C (S) $3400
- · Z (S) $3400
1910.305 E01
- Issued
- Jul 25, 2013
- Penalty
- Initial $3,400 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panel board enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: The protective covering of a junction box, located on the wash line of the facility, was missing and did not prevent moisture from accumulating within the enclosure.
Recent events (3)
- · F (S) $0
- · C (S) $3400
- · Z (S) $3400
1910.157 C04
- Issued
- Jul 25, 2013
- Abate by
- Aug 4, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition: On or about 03/08/2013, two of the company's portable fire extinguishers were missing the safety pin. The portable fire extinguishers include, but are not limited to the following: a. The Amerex (10 lbs.), ABC rechargeable fire extinguisher, located on a pillar, in the wash bay area; b. The ABC rechargeable fire extinguisher, located on a fork truck, in the shipping and receiving department.
Recent events (3)
- · F (O) $0
- · C (O) $0
- · Z (O) $0
More inspections at Qualawash Holdings, LLC
View Qualawash Holdings, LLC's full OSHA safety record →
More inspections in this industry (NAICS 562998)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338969397.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.