Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: SERVICE ELECTRIC COMPANY

Fatality or catastrophe inspection · Safety discipline

On , OSHA opened a fatality or catastrophe safety inspection of SERVICE ELECTRIC COMPANY in 3621 CR 2300, PANAMA CITY, FL 32405 (NAICS 238210). OSHA activity number 338972672.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Service Electric Company for free Get an email when a new federal OSHA severe-injury report for Service Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
3621 CR 2300
City
PANAMA CITY
State
FL
ZIP
32405
Mailing
P.O. BOX 3656 1631 E. 25TH STREET, CHATTANOOGA, TN 37404
Inspection type
Fatality or catastrophe (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
Yes
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
8
Ownership type
Private (A)

4 citations on file for this inspection.

1926.955 E02

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $7,000 · Current $7,000
29 CFR 1926.955(e)(2):   When removing grounds, the grounding device was not first removed from the line or equipment using insulating tools or other suitable devices:    a.  On or about March 20, 2013, on the west side of Hwy 2300, the ground connected to a guy wire was not properly removed from the overhead power line, exposing employees to an electrical hazard.
Recent events (2)
  • · I (S) $7000
  • · Z (S) $7000

1926.955 C03

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.955(c)(3): Where there is a possibility of the conductor accidentally contacting an energized circuit or receiving a dangerous induced voltage buildup, to further protect the employee from the hazards of the conductor, the conductor being installed or removed shall be grounded or provisions made to insulate or isolate the employee:   a.   On or about April 20, 2013, on the west side of Hwy 2300, employees were not protected and/or isolated from hazards of a conductor that was being removed.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.955 C02

Serious Gravity 10 1 instance 11 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1926.955(c)(2):  Prior to stringing operations a briefing was not held setting forth the plan of operation and specifying the type of equipment to be used, grounding devices and procedures to be followed, crossover methods to be employed, and the clearance authorization required:         a.	On or about March 20, 2013, on the west side of Hwy 2300, prior to employees removing conductors, a briefing was not held that covered all of the special precautions, and procedures to be followed, including but not limited to warnings and instructions on equal potential zones and induced voltages.
Recent events (2)
  • · I (S) $0
  • · Z (S) $7000

1926.503 B01

Deleted Other-than-serious 1 instance 5 exposed
Issued
Jul 10, 2013
Abate by
Aug 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.503(b)(1): The employer did not verify fall protection training by preparing a written certification record:  a.  On or about April 20, 2013, on the west side of Hwy 2300, employees working in bucket trucks performing high power line work were not adequately trained about the hazards of fall protection and the procedures to minimize those hazards.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Service Electric Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338972672.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.