PANAMA CITY, FL ·
OSHA Inspection: SERVICE ELECTRIC COMPANY
Fatality or catastrophe inspection · Safety discipline
At a glance
On , OSHA opened a fatality or catastrophe safety inspection of SERVICE ELECTRIC COMPANY in 3621 CR 2300, PANAMA CITY, FL 32405 (NAICS 238210). OSHA activity number 338972672.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SERVICE ELECTRIC COMPANY
- Site address
- 3621 CR 2300
- City
- PANAMA CITY
- State
- FL
- ZIP
- 32405
- Mailing
- P.O. BOX 3656 1631 E. 25TH STREET, CHATTANOOGA, TN 37404
What kind of inspection was it?
- Inspection type
- Fatality or catastrophe (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 8
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1926.955 E02
- Issued
- Jul 10, 2013
- Abate by
- Aug 5, 2013
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1926.955(e)(2): When removing grounds, the grounding device was not first removed from the line or equipment using insulating tools or other suitable devices: a. On or about March 20, 2013, on the west side of Hwy 2300, the ground connected to a guy wire was not properly removed from the overhead power line, exposing employees to an electrical hazard.
Recent events (2)
- · I (S) $7000
- · Z (S) $7000
1926.955 C03
- Issued
- Jul 10, 2013
- Abate by
- Aug 5, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.955(c)(3): Where there is a possibility of the conductor accidentally contacting an energized circuit or receiving a dangerous induced voltage buildup, to further protect the employee from the hazards of the conductor, the conductor being installed or removed shall be grounded or provisions made to insulate or isolate the employee: a. On or about April 20, 2013, on the west side of Hwy 2300, employees were not protected and/or isolated from hazards of a conductor that was being removed.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1926.955 C02
- Issued
- Jul 10, 2013
- Abate by
- Aug 5, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1926.955(c)(2): Prior to stringing operations a briefing was not held setting forth the plan of operation and specifying the type of equipment to be used, grounding devices and procedures to be followed, crossover methods to be employed, and the clearance authorization required: a. On or about March 20, 2013, on the west side of Hwy 2300, prior to employees removing conductors, a briefing was not held that covered all of the special precautions, and procedures to be followed, including but not limited to warnings and instructions on equal potential zones and induced voltages.
Recent events (2)
- · I (S) $0
- · Z (S) $7000
1926.503 B01
- Issued
- Jul 10, 2013
- Abate by
- Aug 5, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.503(b)(1): The employer did not verify fall protection training by preparing a written certification record: a. On or about April 20, 2013, on the west side of Hwy 2300, employees working in bucket trucks performing high power line work were not adequately trained about the hazards of fall protection and the procedures to minimize those hazards.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at Service Electric Company
View Service Electric Company's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338972672.