Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ACOUSTIC TECHNOLOGY, INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ACOUSTIC TECHNOLOGY, INC in 30 JEFFRIES STREET, EAST BOSTON, MA 02128 (NAICS 334290). OSHA activity number 338973324.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Acoustic Technology, INC — free Get an email when a new federal OSHA severe-injury report for Acoustic Technology, INC is published. One employer, no account, unsubscribe in one click.
Site address
30 JEFFRIES STREET
City
EAST BOSTON
State
MA
ZIP
02128
Mailing
30 JEFFRIES STREET, EAST BOSTON, MA 02128
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334290
Employees
33
Ownership type
A

11 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 1 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $2,380 · Current $1,666 Reduced
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(I) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to laceration and amputation hazards from the unintended restart of a metal cutting saw:  Storage/Hardware Room:  Employees were exposed to laceration/amputation hazards while operating the JET bandsaw in the event of an unintended restart of the saw after a power outage.
Recent events (2)
  • — I (S) $1666
  • — Z (S) $2380

1910.37 B04

Serious Gravity 5 2 instances 10 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $2,380 · Current $1,666 Reduced
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:  Storage/Warehouse Area:  In the event of an emergency, there were no signs indicating direction of travel in this area.  The door to the lobby that was part of the exit route was not marked.  The doors were not visible to employees in this area       Lobby:  There was an exit sign over the door to the first loading dock did not indicate that the direction of travel was to the right.
Recent events (2)
  • — I (S) $1666
  • — Z (S) $2380

1910.37 B05

Serious Gravity 5 2 instances 15 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  The doors in the following locations that were not part of an exit route were not marked:     1.  Double doors between Assembly and the front storage room;     2.  Double doors on the first landing from the basement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.151 C

Serious Gravity 1 1 instance 3 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $1,785 · Current $1,250 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  Basement testing area:  There was no eyewash or other means of flushing the eyes and/or body where employees were exposed to the potential of burns from sulphuric acid in the 12-volt lead-acid batteries used for testing the alarm systems.
Recent events (2)
  • — I (S) $1249.5
  • — Z (S) $1785

1910.178 L01 I

Serious Gravity 5 1 instance 3 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $2,380 · Current $1,666 Reduced
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l):  Facility:  Employees operating the walker-stacker were not trained and evaluated as required.
Recent events (2)
  • — I (S) $1666
  • — Z (S) $2380

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
May 29, 2013
Abate by
Jul 16, 2013
Penalty
Initial $2,975 · Current $2,083 Reduced
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by moving parts:  Storage/Hardware Room:  Employees were exposed to amputation/laceration hazards while operating the JET bandsaw where approximately 8-inches of the unused portion of the blade was not guarded.
Recent events (2)
  • — I (S) $2082.5
  • — Z (S) $2975

1910.303 B07 I

Serious Gravity 5 10 instances 3 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $2,975 · Current $2,083 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  Testing Lab (Wind-Starr's office) - Employes were exposed to electric shock and arc flash/blast hazards from circuit breaker panels where breakers were removed and openings were not covered.
Recent events (2)
  • — I (S) $2082.5
  • — Z (S) $2975

1910.303 G01

Serious Gravity 1 3 instances 1 exposed
Issued
May 29, 2013
Abate by
Jul 16, 2013
Penalty
Initial $1,785 · Current $1,250 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  Testing Lab (Wind-Starr's Office):  Access to two of the circuit breaker panels in the wall were blocked by a bookshelf.  Access to a third panel was limited by a desk placed in front of the panel.
Recent events (2)
  • — I (S) $1249.5
  • — Z (S) $1785

1910.305 G01 IV A

Serious Gravity 5 10 instances 30 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $2,380 · Current $1,666 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Facility:  Extension cords and Relocatable Power Taps were "daisy-chained" and used in place of permanent wiring in multiple locations throughout the facility including the Basement Testing Lab, the Assembly Room, and the Test lab (Wind-Starr's office).
Recent events (2)
  • — I (S) $1666
  • — Z (S) $2380

1910.212 B

Other-than-serious 2 instances 2 exposed
Issued
May 29, 2013
Abate by
May 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:  Assembly Area:  The Craftsman drill press and the Rigid drill press were not bolted to the floor.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 3 instances 1 exposed
Issued
May 29, 2013
Abate by
Jul 16, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  Test lab (Wind-Starr's office):  The labels on the circuit breakers in the three panels in the wall were not updated to reflect their current use.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338973324.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.