2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: STONE & WEBSTER CONSTRUCTION INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of STONE & WEBSTER CONSTRUCTION INC. in MO HIGHWAY CC & ROUTE O, FULTON, MO 65251 (NAICS 221113). OSHA activity number 338994007.

Watch Stone & Webster Construction INC. — free Get an email when a new federal OSHA severe-injury report for Stone & Webster Construction INC. is published. One employer, no account, unsubscribe in one click.
Site address
MO HIGHWAY CC & ROUTE O
City
FULTON
State
MO
ZIP
65251
Mailing
4171 ESSEN LANE, BATON ROUGE, LA 70809
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221113
Employees
5686
Ownership type
A

6 citations on file for this inspection.

1910.269 C

Deleted Serious Gravity 10 3 instances 6 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.269(c): The employee in charge did not conduct a job briefing with the employees involved before they started each job, including at least the following subjects: hazards associated with the job, work procedures involved, and special precautions:  At the AMEREN-UE Calloway Nuclear Plant, switchyard, specifically at Bus B, 52-4, an arc flash occurred on or about 04/02/13 severely burning employees.  The job briefing performed prior to the arc flash did not contain the following elements:  a/  Ensuring that the conductors inside of Bus B, 52-4, were isolated from all sources of electrical energy prior to the start of work.  b/  Identifying the minimum safe working conditions.  c/  Identifying the type of personal protective equipment to be worn.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.269 D02 VIII A

Deleted Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.269(d)(2)(viii)(A): Retraining was not provided for all authorized and affected employees whenever there was a change in their job assignments, a change in machines, equipment, or processes that present a new hazard or whenever there was a change in the energy control procedures:  At the AMEREN-UE Calloway Nuclear Plant, switchyard, specifically at Bus B, 52-4, an arc flash occurred on or about 04/02/13 severely burning employees. The employees, normally assigned to work with electrical equipment rated at 480 volts or less, were tasked with grounding Bus B, 52-4, rated at 13.8 kv.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.269 D06 III

Deleted Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.269(d)(6)(iii): All energy isolating devices needed to control the energy to the machine or equipment were not physically located and/or operated in such a manner as to isolate the machine or equipment from energy sources:  At the AMEREN-UE Calloway Nuclear Plant, switchyard, specifically at Bus B, 52-4, an arc flash occurred on or about 04/02/13 severely burning employees. All of the electrical energy isolating devices required to isolate Bus B, 52-4, were not physically located and/or operated prior to the employees attempting to place personnel protective grounds on connectors located inside of this piece of equipment.
Recent events (3)
  • — F (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.269 D06 VII

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $4550.00 Reduced
29 CFR 1910.269(d)(6)(vii): Before starting work on machines or equipment that have been locked out or tagged out, the authorized employee did not verify that isolation and deenergizing of the machine or equipment had been accomplished:    At the AMEREN-UE Calloway Nuclear Plant, switchyard, specifically at Bus B, 52-4, an arc flash occurred on or about 04/02/13 severely burning employees.  Verification that Bus B, 52-4 was isolated from its 13.8kv electrical source was not performed prior to employees attempting to place personnel protective grounds on connectors located inside of this piece of equipment.
Recent events (3)
  • — F (S) $4550
  • — C (S) $7000
  • — Z (S) $7000

1910.269 L02

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $4550.00 Reduced
29 CFR 1910.269(l)(2): The employer did not ensure that no employee(s) approached or took conductive objects closer to exposed energized parts than set forth in Tables R-6 through R-10:    At the AMEREN-UE Calloway Nuclear Plant, switchyard, specifically at Bus B, 52-4, an arc flash occurred on or about 04/02/13 severely burning employees.  Employee(s) approached to within six inches of the live connectors located inside of this piece of equipment.  Bus B, 52-4 was powered by 13.8kv at the time.  Table R-6 requires that a minimum approach distance of 26 inches be maintained for that amount of voltage.
Recent events (3)
  • — F (S) $4550
  • — C (S) $7000
  • — Z (S) $7000

1910.335 A01 I

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $4550.00 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    At the AMEREN-UE Calloway Nuclear Plant, switchyard, specifically at Bus B, 52-4, an arc flash occurred on or about 04/02/13 severely burning employees. The employees were not provided with or wore suitable personnel protective equipment such as 40-calorie suits or the equivalent prior to completely isolating this piece of equipment from its 13.8kv electrical source.
Recent events (3)
  • — F (S) $4550
  • — C (S) $7000
  • — Z (S) $7000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338994007.