SAINT ANN, MO —
OSHA Inspection: UNION ELECTRIC
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of UNION ELECTRIC in 3503 SAN JOSE, SAINT ANN, MO 63074 (NAICS 221112). OSHA activity number 339003436.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNION ELECTRIC
- Site address
- 3503 SAN JOSE
- City
- SAINT ANN
- State
- MO
- ZIP
- 63074
- Mailing
- 1901 CHOUTEAU AVE., SAINT LOUIS, MO 63166
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221112
- Employees
- 51
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.269 L02 I
- Issued
- Jun 17, 2013
- Abate by
- Aug 2, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(l)(2)(i): The employer failed to ensure that no employee approached or took any conductive object closer to exposed energized parts than set forth in Tables R-6 through R-10 when the employee was not insulated from the energized part (rubber gloves or rubber gloves and insulating sleeves are considered insulation): On or about April 11, 2013, during storm restoration, an employee was electrocuted while on a utility pole and contacted a 7200 V primary line. The employee was wearing leather gloves.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
1910.269 M03 V
- Issued
- Jun 17, 2013
- Abate by
- Aug 2, 2013
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(m)(3)(v): After the applicable requirements in paragraphs (m)(3)(i) through (m)(3)(iv) of this section have been followed, the employee in charge of the work did not obtain a clearance by the system operator, and the lines and equipment to be worked were not tested to ensure that they were de-energized: On or about April 11, 2013, during storm restoration, an employee was electrocuted while on a utility pole and contacted a 7200 V primary line. The primary line had not been tested to ensure it was de-energized.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
More inspections at Union Electric
View Union Electric's full OSHA safety record →
More inspections in this industry (NAICS 221112)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339003436.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.