NEPTUNE, NJ —
OSHA Inspection: NEW JERSEY AMERICAN WATER
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of NEW JERSEY AMERICAN WATER in 311 OLD CORLIES AVE, NEPTUNE, NJ 07753 (NAICS 221310). OSHA activity number 339007601.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEW JERSEY AMERICAN WATER
- Site address
- 311 OLD CORLIES AVE
- City
- NEPTUNE
- State
- NJ
- ZIP
- 07753
- Mailing
- 311 OLD CORLIES AVE, NEPTUNE, NJ 07753
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221310
- Employees
- 30
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.36 E02
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $5,000 · Current $7,000
General-duty citation text
29 CFR 1910.36(e)(2): The door(s) that connected any room to an exit route did not swing out in the direction of exit travel when the room was designed to be occupied by more than 50 people or when the room was a high hazard area. a) Service room: The emergency exit door that connected the service room to the main entrance area did not open in the direction of travel, on or about 4/15/13.
Recent events (3)
- — J (S) $7000
- — C (S) $5000
- — Z (S) $5000
1910.119 N
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(n): The employer did not establish and implement an emergency plan for the entire plant in accordance with the provisions of 29 CFR 1910.38: a) Throughout facility: The employer's emergency action plan did not identify an alternate evacuation route in the event that the wind direction changed and the primary route was compromised, on or about 4/15/13. b) Throughout facility: The employer's emergency action plan did not specifically state what conditions would require an evacuation of the shelter in place location during a chlorine leak, on or about 4/15/13.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.119 D03 I B
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $5,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams did not include information that provided specific identification of equipment that was part of the process. a) Throughout facility: The P&ID did not identify all process equipment according to the current computer system information, on or about 4/15/13. b) Throughout facility: The P&ID listed the vacuum regulating valve information according to the old computer system. The valves were labeled as CLRV-1 and LAV-2 and should have been CLRV 1 and CLRV2, on or about 4/15/13. c) Throughout facility: The P&ID showed globe and gate valves in the drawing where only ball valves existed, on or about 4/15/13.
Recent events (3)
- — J (S) $0
- — C (S) $5000
- — Z (S) $5000
1910.119 F01 I E
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $5,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(f)(1)(i)(E): 29 CFR 1910.119 (f)(1)(i)(E) The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information that addressed the steps for each operating phase, including emergency operations. a) Feed room: The employer's standard operating procedures in the emergency response plan on pages 19-21 provided incorrect information for shutting down of the evaporators in the event of a chlorine leak. The plan instructs use of a standby evaporator that does not exist, on or about 4/15/13. b) Throughout facility: The employer's emergency action plan did not provide instruction on how to preserve the air quality at the shelter in place location in the facility, such as, but not limited to, when to close windows or shut down the HVAC system, on or about 4/15/13.
Recent events (3)
- — J (S) $0
- — C (S) $5000
- — Z (S) $5000
1910.119 J04 I
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $5,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment a) Scrubber room: Inspections of the Environmental Systems Emergency Gas Retro-fit Dry Scrubber System did not follow the manufacturer's recommended maintenance practices in section 4.0.2 page 4, such as, but not limited to, checking the fan wheel for wear or corrosion and cleaning the wheel as required, checking the v-belt for proper alignment and tension and replacement as necessary, lubricating the coupling of the direct drive units and checking for alignment and lubricating the bearings, on or about 4/15/13.
Recent events (3)
- — J (S) $0
- — C (S) $5000
- — Z (S) $5000
1910.119 J06 II
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(j)(6)(ii): Appropriate checks and inspections were not performed to assure that equipment was installed properly and consistent with design specifications and the manufacturer's instructions. a) Chlorine storage room: Appropriate checks and inspections were not performed to assure that valves and lead washers were connected to the one ton cylinders during installation using the proper torqueing values and wrenches as recommended by the manufacturer and Chlorine Institute Pamphlet 155, on or about 4/15/13.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.147 C04 I
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $5,000 · Current $7,000
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) Production Areas - A site specific written lockout program identifying the specific sources of energy of production equipment, the magnitudes of that energy, and the specific procedures to de-energize those energy sources, was not developed for equipment including, but not limited to pumps, sludge presses, chlorinators, and evaporators. On or about 4/15/13. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (S) $7000
- — C (S) $5000
- — Z (S) $5000
1910.303 G02 I
- Issued
- Oct 2, 2013
- Penalty
- Initial $5,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Pipe gallery: Live electrical components operating at 120 volts in the back of the chlorine analyzing unit were not protected from accidental contact by such means as, but not limited to, enclosures or approved cabinets, on or about 4/15/13.
Recent events (3)
- — J (O) $3500
- — C (S) $5000
- — Z (S) $5000
1910.119 D02 I A
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(d)(2)(i)(A): The process safety information did not include information pertaining to the technology of the process: a) Chlorine storage and feed rooms: The employer did not develop a block flow diagram for 28,000 pounds of chlorine used in a water treatment process, on or about 6/11/12.
Recent events (3)
- — J (O) $0
- — C (O) $0
- — Z (O) $0
1910.119 E03 I
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(e)(3)(i): The process hazard analysis did not address the hazards of the process. a) Throughout facility: The employer's PHA did not address the buildup of nitrogen trichloride in the system as recommended by Chlorine Institute Pamphlet number 152, on or about 4/15/13.
Recent events (3)
- — J (O) $0
- — C (O) $0
- — Z (O) $0
1910.146 C04
- Issued
- Oct 2, 2013
- Abate by
- Oct 29, 2013
- Penalty
- Initial $0 · Current $3,500
General-duty citation text
29 CFR 1910.146(c)(4): When the employer decided that its employees would enter permit spaces, the employer did not develop and implement a written permit space entry program that complied with 29 CFR 1910.146: a) Establishment - Site specific permit required confined space entry procedures were not developed for employees who entered permit spaces such as, but not limited to the vault under the drain of the purification units. On or about 4/15/13. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
- — J (O) $3500
- — C (O) $0
- — Z (O) $0
More inspections at NEW Jersey American Water
View NEW Jersey American Water's full OSHA safety record →
More inspections in this industry (NAICS 221310)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339007601.