OSHA Inspection: HARTFORD FREEZERS A DIVISION OF CONNECTICUT FREEZERS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HARTFORD FREEZERS A DIVISION OF CONNECTICUT FREEZERS, INC. in 241 PARK AVENUE, EAST HARTFORD, CT 06108 (NAICS 493120). OSHA activity number 339008161.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hartford Freezers a Division of Connecticut Freezers, INC. — free Get an email when a new federal OSHA severe-injury report for Hartford Freezers a Division of Connecticut Freezers, INC. is published. One employer, no account, unsubscribe in one click.
Site address
241 PARK AVENUE
City
EAST HARTFORD
State
CT
ZIP
06108
Mailing
276 MCARTHUR DRIVE, NEW BEDFORD, MA 02740
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
11
Ownership type
A

8 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 2 instances 11 exposed
Issued
Jul 1, 2013
Abate by
Nov 16, 2013
Penalty
Initial $3,851 · Current $2,696 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that, employees were exposed to fire, explosion and corrosive hazards:      Warehouse Facility:  On, or about, April 16, 2013, employees were exposed to potential releases of anhydrous ammonia from the closed loop refrigeration system installed in the facility in that,    A.  Engine Room:  An adequate source of make-up air had not been provided for the ventilation system.  Also, the door providing access to/egress from the room was not a tight fitting, self-closing fire door.    B.  Pump Package Room:  An adequate source of make-up air had not been provided for the ventilation system.  No empirical data was available to show that leaving the door open to the room would be sufficient.  Also, the room was required to be provided with a tight fitting, self-closing fire door in order to separate the equipment in the room from the rest of facility.
Recent events (2)
  • — I (S) $2695.7
  • — Z (S) $3851

1910.24 H

Serious Gravity 5 3 instances 11 exposed
Issued
Jul 1, 2013
Abate by
Aug 16, 2013
Penalty
Initial $3,080 · Current $2,156 Reduced
29 CFR 1910.24(h): Standard railings were not provided on the open sides of all exposed stairways and stair platforms and/or handrails were not provided on least one side of closed stairways, preferably on the right side descending:  On, or about, April 16, 2013, in the following locations, fixed industrial stairs were not provided with adequate railings and/or hand rails:  A.  Engine Room:  Stairway leading to roof. B.  Maintenance Shop:  Rear exit door stairs. C.  Main Entrance:  Access stairs.
Recent events (2)
  • — I (S) $2156
  • — Z (S) $3080

1910.36 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 1, 2013
Abate by
Nov 16, 2013
Penalty
Initial $3,851 · Current $2,696 Reduced
29 CFR 1910.36(b)(1):  At least two exit routes were not available in a workplace to permit prompt evacuation of employees and other building occupants during an emergency, except as allowed in paragraph (b)(3) of this section:    Engine Room:  On, or about, April 16, 2013, only one exit was provided from the Engine Room.  The length of the room exceeded the common path of travel exemptions listed in National Fire Protection Association Standard NFPA 101 Life Safety Code.
Recent events (2)
  • — I (S) $2695.7
  • — Z (S) $3851

1910.36 E01

Serious Gravity 5 1 instance 11 exposed
Issued
Jul 1, 2013
Abate by
Aug 16, 2013
Penalty
Initial $3,080 · Current $2,156 Reduced
29 CFR 1910.36(e)(1): A side-hinged door was not used to connect any room to an exit route:   Rear Rail Dock Corridor:  On, or about, April 22, 2013, employees were required to pass through a sliding door into the maintenance shop to access the exterior exit door.
Recent events (2)
  • — I (S) $2156
  • — Z (S) $3080

1910.37 A03

Serious Gravity 5 1 instance 11 exposed
Issued
Jul 1, 2013
Abate by
Aug 16, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit routes were not free and unobstructed. Materials or equipment were placed, either permanently or temporarily, within the exit route:   Maintenance Shop:  On, or about, April 22, 2013, an order selecting truck was parked in the egress path between the maintenance shop entrance door and the exterior exit door.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B04

Serious Gravity 5 1 instance 11 exposed
Issued
Jul 1, 2013
Abate by
Aug 16, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:  Rear Rail Dock Corridor:  On, or about, April 22, 2013, directional signs were not provided to direct employees to exit doors after the passed through the main corridor overhead door pass-through.  Once through the overhead door, there were no signs to indicate the location of the exit doors.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 A04

Serious Gravity 1 1 instance 11 exposed
Issued
Jul 1, 2013
Abate by
Aug 16, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:  Side Corridor near Office:  On, or about, April 22, 2013, the lighting for EXIT sign provided over the exterior exit door was not maintained in an operable condition.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.151 C

Serious Gravity 5 2 instances 1 exposed
Issued
Jul 1, 2013
Abate by
Nov 16, 2013
Penalty
Initial $3,851 · Current $2,696 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:   On, or about, April 16, 2013, in the following locations, eyewash units had not been installed outside of rooms that housed ammonia mechanical refrigeration equipment:    A.  Engine Room located above main corridor.  B.  Pump Package Room located next to the main corridor.
Recent events (2)
  • — I (S) $2695.7
  • — Z (S) $3851