Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: LEVE AGRIMAN

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of LEVE AGRIMAN in 194 N. MAIN STREET, FREDERICKTOWN, OH 43019 (NAICS 424510). OSHA activity number 339008559.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Leve Agriman for free Get an email when a new federal OSHA severe-injury report for Leve Agriman is published. One employer, no account, unsubscribe in one click.
Establishment
LEVE AGRIMAN
Site address
194 N. MAIN STREET
City
FREDERICKTOWN
State
OH
ZIP
43019
Mailing
194 N. MAIN STREET, FREDERICKTOWN, OH 43019
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
6
Ownership type
A

9 citations on file for this inspection.

1910.272 J01

Serious Gravity 5 1 instance 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $2,000 · Current $700 Reduced
29 CFR 1910.272(j)(1):  The employer shall develop and implement a written housekeeping program that establishes the frequency and method(s) determined best to reduce accumulations of fugitive grain dust on ledges, floors, equipment, and other exposed surfaces:     a.  At the facility, the employer did not develop and implement a written housekeeping program that established the frequency and method(s) determined best to reduce accumulations of fugitive grain dust on ledges, floors, equipment, and other exposed surfaces in areas including, but not limited to, the following:  all levels of the South Mill, South Mill Mixer Area, and North Mill.
Recent events (2)
  • · I (S) $700
  • · Z (S) $2000

1910.272 J04

Serious Gravity 5 1 instance 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.272(j)(4):  Grain and product spills shall not be considered fugitive grain dust accumulations.  However, the housekeeping program shall address the procedures for removing such spills from the work area:     a.  At the facility, the employer did not develop and implement a written housekeeping program that established the procedures for removing product spills throughout the mill.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.272 J02 II

Serious Gravity 5 2 instances 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $2,000 · Current $700 Reduced

Hazardous substances E200M102M104

29 CFR 1910.272(j)(2)(ii):  The employer shall immediately remove any fugitive grain dust accumulations whenever they exceed 1/8 inch (.32 cm) at priority housekeeping areas, pursuant to the housekeeping program, or shall demonstrate and assure, through the development and implementation of the housekeeping program, that equivalent protection is provided:     a.  In the basement of the South Mill, fugitive grain dust accumulations of .140 to 5 inches which had covered areas such as the floor surfaces, pit floor, floor ledges, wall ledges, stair steps, section of pipe on floor, base of support column, boot for South leg, South pit auger, wood surfaces, U-trough, and snap switch for lights were not immediately removed.     b.  In the basement of the South Mill Mixer Area, fugitive grain dust accumulations of .148 to 6 inches which had covered areas such as the floor surfaces, steps on stepladder, duplex receptacle on column near new leg, unused Prater grinder, disconnect for molasses pump, wooden wall ledges, concrete ledge, horizontal board on column, disconnect for corn auger motor, motor for unused grinder, floor of electrical room, and floor of freight elevator were not immediately removed.
Recent events (2)
  • · I (S) $700
  • · Z (S) $2000

1910.307 C

Serious Gravity 5 6 instances 3 exposed
Issued
May 29, 2013
Abate by
Jan 3, 2014
Penalty
Initial $2,000 · Current $700 Reduced

Hazardous substances E101M102M104

29 CFR 1910.307(c):  Electrical installations.  Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location.  Requirements for each of these options are as follows:    a.  In the basement of the South Mill, electrical equipment including a snap switch for lights in a Class II, Division 1 location was not intrinsically safe, approved for a Class II, Division 1 location, or safe for a Class II, Division 1 location.    b.  In the basement of the South Mill Mixer Area, electrical equipment including, but not limited to, the duplex receptacle on the column near the new leg, disconnect for the molasses pump, and disconnect for the corn auger motor in a Class II, Division 1 location was not intrinsically safe, approved for a Class II, Division 1 location, or safe for a Class II, Division 1 location.    c.  In the electrical room in the basement of the South Mill Mixer Area, electrical equipment including, but not limited to, the circuit breaker box for the office and a duplex receptacle with a heat tape cord plugged into the receptacle in a Class II, Division 2 location was not intrinsically safe, approved for a Class II, Division 2 location, or safe for a Class II, Division 2 location; or the electrical room was not reclassified as a non-hazardous location by providing positive pressure ventilation in conjunction with a self-closing door with seals and ensuring that the room was constructed to prevent the entrainment of grain dust.    d.  On the main floor of the South Mill, electrical equipment including, but not limited to, the fluorescent ceiling light plugged into an extension cord and duplex receptacle, incandescent light plugged into a duplex receptacle, 4-plex receptacle with a Bruchbuhler scale plugged into it, fluorescent ceiling light plugged into a duplex receptacle, disconnect for the exhaust fan, reset box for the South elevator leg, and a Power Twin vacuum (S/N:  3301) in a Class II, Division 2 location was not intrinsically safe, approved for a Class II, Division 2 location, or safe for a Class II, Division 2 location.    e.  In the electrical room on the second floor of the South Mill Mixer Area, electrical equipment including, but not limited to, the duplex receptacle and disconnect boxes/reset boxes for the new leg, corn leg, screw augers 1 and 3, grain screw auger, blue mixer, orange mixer, and crimper in a Class II, Division 2 location was not intrinsically safe, approved for a Class II, Division 2 location, or safe for a Class II, Division 2 location; or the electrical room was not reclassified as a non-hazardous location by providing positive pressure ventilation in conjunction with a self-closing door with seals and ensuring that the room was constructed to prevent the entrainment of grain dust.     f.  On the main floor of the South Mill Mixer Area, electrical equipment including, but not limited to, the radio and 25 foot extension cord plugged into the duplex receptacle in a Class II, Division 2 location was not intrinsically safe, approved for a Class II, Division 2 location, or safe for a Class II, Division 2 location.
Recent events (2)
  • · I (S) $700
  • · Z (S) $2000

1910.307 B

Serious Gravity 5 1 instance 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $0 · Current $0

Hazardous substances E101M102M104

29 CFR 1910.307(b):  Documentation.  All areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007 shall be properly documented.  This documentation shall be available to those authorized to design, install, inspect, maintain, or operate electric equipment at the location:   a.  All areas designated as hazardous (classified) locations under the Class and Division system were not properly documented for the facility including, but not limited to, the following areas:  South mill basement, South mill main floor, South mill mixer area basement, South mill mixer area main floor, and South mill mixer area second floor.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.145 C02 I

Other-than-serious 4 instances 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.145(c)(2)(i): Caution signs shall be used only to warn against potential hazards or to caution against unsafe practices:   a.  At the office entrance to the South Mill, the employer did not have a combustible dust hazard sign to warn against potential deflagration and explosion hazards from grain dust atmospheres that may occur due to the handling of grain.   b.  At the West entrance to the South Mill, the employer did not have a combustible dust hazard sign to warn against potential deflagration and explosion hazards from grain dust atmospheres that may occur due to the handling of grain.   c.  At the West entrance to the South Mill Mixer Area, the employer did not have a combustible dust hazard sign to warn against potential deflagration and explosion hazards from grain dust atmospheres that may occur due to the handling of grain.   d.  At the North entrance to the South Mill Mixer Area, the employer did not have a combustible dust hazard sign to warn against potential deflagration and explosion hazards from grain dust atmospheres that may occur due to the handling of grain.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.272 M03

Other-than-serious 1 instance 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.272(m)(3):  A certification record shall be maintained of each inspection, performed in accordance with this paragraph (m), containing the date of the inspection, the name of the person who performed the inspection and the serial number, or other identifier, of the equipment specified in paragraph (m)(1)(i) of this section that was inspected:  a.  At the facility, the employer did not maintain certification records for inspections performed on equipment including, but not limited to, the following:  bucket elevators and Roskamp crimper(S/N: 2887).
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.1200 E01

Other-than-serious 1 instance 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(e)(1):  Employers shall develop, implement, and maintain at each workplace, a written hazard communication program which at least describes how the criteria specified in paragraphs (f), (g), and (h) of this section for labels and other forms of warning, material safety data sheets, and employee information and training will be met, and which also includes the following:   a.  At the facility, the employer did not have a written hazard communication program which described how the criteria specified in paragraphs (f), (g), and (h) of this section for labels and other forms of warning, material safety data sheets, and employee information and training would be met.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.1200 H01

Other-than-serious 1 instance 3 exposed
Issued
May 29, 2013
Abate by
Jul 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(h)(1):  Employers shall provide employees with effective information and training on hazardous chemicals in their work area at the time of their initial assignment, and whenever a new physical or health hazard the employees have not previously been trained about is introduced into their work area.  Information and training may be designed to cover categories of hazards (e.g., flammability, carcinogenicity) or specific chemicals.  Chemical-specific information must always be available through labels and material safety data sheets:  a.  At the facility, the employer did not provide hazard communication training for employees who were exposed to hazardous chemicals such as gasoline, grease, 10W-40 oil, and Blaster.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View Leve Agriman's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339008559.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.