Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: TWIN WILLOWS NURSING CENTER, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of TWIN WILLOWS NURSING CENTER, INC. in 1600 N BROADWAY, SALEM, IL 62881 (NAICS 623110). OSHA activity number 339041576.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Twin Willows Nursing Center, INC. for free Get an email when a new federal OSHA severe-injury report for Twin Willows Nursing Center, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1600 N BROADWAY
City
SALEM
State
IL
ZIP
62881
Mailing
PO BOX 370, SALEM, IL 62881
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
55
Ownership type
A

10 citations on file for this inspection.

1910.303 G01 I

Other-than-serious 1 instance 1 exposed
Issued
Oct 29, 2013
Abate by
Nov 4, 2013
Penalty
Initial $1,785 · Current $0 Reduced
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1:    In the Maintenance room, the 480V Federal brand switchgear panels did not have a free working space of a minimum of three feet, creating a fire hazard for employees required to operate the switchgear in an emergency.
Recent events (2)
  • · I (O) $0
  • · Z (S) $1785

1910.305 B02 I

Serious Gravity 1 3 instances 1 exposed
Issued
Oct 29, 2013
Penalty
Initial $1,785 · Current $893 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    Three duplex receptacles on the North wall of the Maintenance Room did not have covers, exposing employees to electric shock hazards.
Recent events (2)
  • · I (S) $893
  • · Z (S) $1785

1910.333 B02 I

Deleted Serious Gravity 1 1 instance 1 exposed
Issued
Oct 29, 2013
Abate by
Nov 8, 2013
Penalty
Initial $1,785 · Current $0 Reduced
29 CFR 1910.333(b)(2)(i): The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:  The employer did not prepare or provide a copy of locking and tagging requirements for employees working on or near exposed deenergized parts upon request.  Employees were exposed to unexpected energization of equipment due to improper lockout.
Recent events (2)
  • · I (S) $0
  • · Z (S) $1785

1910.333 B02 III A

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 29, 2013
Abate by
Nov 8, 2013
Penalty
Initial $0 · Current $893
29 CFR 1910.333(b)(2)(iii)(A): The lock was not attached so as to prevent persons from operating the disconnecting means unless they resorted to undue force or the use of tools:    The employer did not insure that a lock and tag were affixed to disconnecting means used to deenergize equipment on which work is to be performed.  The lock is to be so attached as to prevent unwanted persons from operating the disconnect and to necessitate undue force or the use of tools to bypass the lock.     a) The cabinet housing the breaker panel in the kitchen area is locked by maintenance when they service the garbage disposal, within the last 4 months, and the nursing staff have keys to the cabinet and could interfere with the maintenace lockout, exposing the maintenance employee to electric shock and unintended energization hazards.
Recent events (2)
  • · I (S) $893
  • · Z (S) $0

1910.1200 H01

Other-than-serious 1 instance 1 exposed
Issued
Oct 29, 2013
Abate by
Nov 18, 2013
Penalty
Initial $1,785 · Current $0 Reduced
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:    The employer did not provide Hazard Communication training to all housekeeping employees, on issues such as, but not limited to, Neutral Disinfectant, potentially exposing them to skin dermatitis.
Recent events (2)
  • · I (O) $0
  • · Z (S) $1785

1904.40 A

Other-than-serious 1 instance 1 exposed
Issued
Oct 29, 2013
Penalty
Initial $595 · Current $298 Reduced
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours:     Twin Willows Nursing Center, Inc., 1600 N. Broadway Ave., Salem, IL 62881:        On or about 5/3/13, the employer failed to provide a copy of the injury and illness records for 2009 (OSHA 300 log, 300A summary and 301 forms) to an authorized representative.
Recent events (2)
  • · I (O) $298
  • · Z (O) $595

1904.40 A

Other-than-serious 1 instance 1 exposed
Issued
Oct 29, 2013
Penalty
Initial $595 · Current $0 Reduced
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours:    Twin Willows Nursing Center, Inc., 1600 N. Broadway Ave., Salem, IL 62881:      On or about 5/3/13, the employer failed to provide a copy of the injury and illness records for 2010 (OSHA 300 log, 300A summary and 301 forms) to the authorized representative.
Recent events (2)
  • · I (O) $0
  • · Z (O) $595

1904.40 A

Other-than-serious 1 instance 1 exposed
Issued
Oct 29, 2013
Penalty
Initial $595 · Current $298 Reduced
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours:    Twin Willows Nursing Center, Inc., 1600 N. Broadway Ave., Salem, IL 62881:     On or about 5/3/13, the employer failed to provide a copy of the injury and illness records for 2011 (OSHA 300 log, 300A summary and 301 forms) to the authorized representative.
Recent events (2)
  • · I (O) $298
  • · Z (O) $595

1904.40 A

Other-than-serious 1 instance 1 exposed
Issued
Oct 29, 2013
Penalty
Initial $595 · Current $0 Reduced
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours:    Twin Willows Nursing Center, Inc., 1600 N. Broadway Ave., Salem, IL 62881:    On or about 5/3/13, the employer failed to provide a copy of the injury and illness records for 2012 (OSHA 300 log, 300A summary and 301 forms) to the authorized representative.
Recent events (2)
  • · I (O) $0
  • · Z (O) $595

1904.40 A

Other-than-serious 1 instance 1 exposed
Issued
Oct 29, 2013
Penalty
Initial $595 · Current $0 Reduced
29 CFR 1904.40(a): The employer did not provide an authorized government representative the records within the four business hours:     Twin Willows Nursing Center, Inc., 1600 N. Broadway Ave., Salem, IL 62881:    On or about 5/3/13, the employer failed to provide a copy of the injury and illness records for 2013 (OSHA 300 log and 301 forms) to the authorized representative.
Recent events (2)
  • · I (O) $0
  • · Z (O) $595

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339041576.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.