CHESTER, NY —
OSHA Inspection: NEXANS ENERGY USA, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NEXANS ENERGY USA, INC. in 25 OAKLAND AVE., CHESTER, NY 10918 (NAICS 332618). OSHA activity number 339057747.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEXANS ENERGY USA, INC.
- Site address
- 25 OAKLAND AVE.
- City
- CHESTER
- State
- NY
- ZIP
- 10918
- Mailing
- 25 OAKLAND AVE., CHESTER, NY 10918
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332618
- Employees
- 160
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.215 B09
- Issued
- Aug 7, 2013
- Abate by
- Aug 22, 2013
- Penalty
- Initial $3,400 · Current $2,550 Reduced
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: A) Maintenance Shop - On or about May 8, 2013, the United States Electric Tool grinder (Serial #314737) was not equipped with tongue guards on the two abrasive wheels; unguarded opening was approximately 3/4".
Recent events (2)
- — I (S) $2550
- — Z (S) $3400
1910.303 B07 I
- Issued
- Aug 7, 2013
- Abate by
- Aug 22, 2013
- Penalty
- Initial $3,400 · Current $2,550 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. A) Armory Department - On or about May 8, 2013, the Allen Bradley Bulletin 800R switchbox on BX-17 was missing a knockout to block off the opening for the lower switch.
Recent events (2)
- — I (S) $2550
- — Z (S) $3400
1910.147 C05 II B
- Issued
- Aug 7, 2013
- Abate by
- Aug 22, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(5)(ii)(B): Lockout and tagout devices were not standardized within the facility in at least one of the following criteria: color; shape; or size: A) Maintenance Shop - On or about May 8, 2013, the lockout devices in the cabinet were not standardized in color, shape, or size.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Nexans Energy USA, INC.
View Nexans Energy USA, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332618)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339057747.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.