Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SOUTHWESTERN CREATIONS LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SOUTHWESTERN CREATIONS LLC in P.O. BOX 69 110 POPLAR STREET, SOUTH WEST CITY, MO 64863 (NAICS 331222). OSHA activity number 339058927.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Southwestern Creations LLC — free Get an email when a new federal OSHA severe-injury report for Southwestern Creations LLC is published. One employer, no account, unsubscribe in one click.
Site address
P.O. BOX 69 110 POPLAR STREET
City
SOUTH WEST CITY
State
MO
ZIP
64863
Mailing
P.O. BOX 69 110 POPLAR STREET, SOUTH WEST CITY, MO 64863
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331222
Employees
38
Ownership type
A

2 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 5 1 instance 1 exposed
Issued
May 30, 2013
Abate by
Jun 25, 2013
Penalty
Initial $2,380 · Current $1,666 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A):  (a)  The electrical cabinet housing live parts energized to 480 volts AC was not guarded by accidental contact and accessible only to qualified persons.  NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM.  FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19
Recent events (2)
  • — I (S) $1666
  • — Z (S) $2380

1910.305 B01 I

Serious Gravity 5 1 instance 1 exposed
Issued
May 30, 2013
Abate by
Jun 25, 2013
Penalty
Initial $2,380 · Current $1,666 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:  (a) The cable entering the box at the #1 Wire Straightner machine had the flex conduit broken and conductors exposed to  damage.   NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM.  FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19
Recent events (2)
  • — I (S) $1666
  • — Z (S) $2380

View Southwestern Creations LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339058927.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.