OSHA Inspection: DETROIT FORMING INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DETROIT FORMING INC in 2700 CHURCH ROAD, AURORA, IL 60502 (NAICS 326199). OSHA activity number 339059800.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Detroit Forming INC — free Get an email when a new federal OSHA severe-injury report for Detroit Forming INC is published. One employer, no account, unsubscribe in one click.
Establishment
DETROIT FORMING INC
Site address
2700 CHURCH ROAD
City
AURORA
State
IL
ZIP
60502
Mailing
19100 WEST EIGHT MILE ROAD, SOUTHFIELD, MI 48075
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
37
Ownership type
A

8 citations on file for this inspection.

1910.334 C01

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Dec 9, 2013
Penalty
Initial $4,500 · Current $1,800 Reduced
29 CFR 1910.334(c)(1): Unqualified persons performed testing work on electric circuits or equipment.     Employees who performed voltage testing on energized components up to 220-230v inside panels on machines and equipment such as, but not limited to thermoforming machines, were not qualified to perform testing work on electric circuits or equipment.       Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).     Abatement note:  Qualified persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment (PPE), insulating and shielding materials and insulated tools (see 1910.333(c)(2)).
Recent events (2)
  • — I (S) $1800
  • — Z (S) $4500

1910.332 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Dec 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:      Employees performed voltage testing on energized components up to 220-230v inside panels on machines and equipment such as, but not limited to thermoforming machines. Employees were not trained in and familiar with safety-related work practices such as the use of special precautionary techniques, personal protective equipment (PPE) and insulating and shielding materials.      Abatement documentation is required for this item in accordance with the requirements of 1903.19(d).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B03

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Dec 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(3): Additional Requirements for Qualified Persons.  Qualified persons (those permitted to work on or near exposed energized parts) were not, at a minimum, trained in and familiar with the following:      (i) The skills and techniques necessary to distinguish exposed live parts from other parts of electric equipment.   (ii) The skills and techniques necessary to determine the nominal voltage of exposed live parts, and   (iii) The clearance distances specified in 1910.333(c) and the corresponding voltages to which the qualified person will be exposed.      Employees performed voltage testing on energized components up to 220-230v inside panels on machines and equipment such as, but not limited to thermoforming machines.  The employees were not trained in and familiar with the additional requirements for qualified persons, as listed above.      Abatement documentation is required for this item in accordance with the requirements of 1903.19(d).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Dec 9, 2013
Penalty
Initial $4,500 · Current $1,700 Reduced
29 CFR 1910.335(a)(1)(i):   Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:         Employees performed voltage testing on energized components and equipment up to 220-230-v on machines such as, but not limited to thermoforming machines. Electrical protective equipment was not provided or utilized, including but not limited to the following, to protect against electrical shock and arc flash/blast injuries:         a) Rubber insulating gloves with leather protectors.   b) Arc-rated long-sleeve shirt and pants or arc-rated coverall.       c) Arc-rated flash suit hood or balaclava.   c) Hearing protection (canal inserts).       Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).           Abatement Note:  For compliance assistance, refer to NFPA 70E national consensus standard, Standard for Electrical Safety in the Workplace - 2012 Edition, www.NFPA.org.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $4500

1910.335 A01 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Dec 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(iv): Employees exposed to the danger of head injury from electric shock or burns due to contact with exposed energized parts did not wear nonconductive head protection:    Employees performed voltage testing on energized components up to 220-230v.  Nonconductive head protection was not worn.    Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).    Abatement Note:  For compliance assistance, refer to NFPA 70E national consensus standard, Standard for Electrical Safety in the Workplace - 2012 Edition, www.NFPA.org.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 V

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Dec 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:      Employees performed voltage testing on energized components up to 220-230v.  An arc-rated face shield was not worn to protect the eyes and face from electric arcs or flashes or from flying debris.        Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).     Abatement Note:  For compliance assistance, refer to NFPA 70E national consensus standard, Standard for Electrical Safety in the Workplace - 2012 Edition, www.NFPA.org.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C06 II

Other-than-serious 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Dec 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(ii): The periodic inspection certification of energy control procedures did not contain the required documentation on identification of the machine or equipment, inspection date, employees included, and the person performing the inspection:    The employer's certification of periodic inspections of the energy control procedures did not contain the required documentation for identification of the machine or equipment and the employees included in the periodic inspection.    Abatement certification is required for this item in accordance with 29 CFR 1903.19(c).    Abatement note:  The certification shall identify the machine or equipment on which the energy control procedure was being utilized, the date of the inspection, the employees included in the inspection, and the person performing the inspection.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.178 L04 III

Other-than-serious 1 instance 2 exposed
Issued
Oct 7, 2013
Abate by
Nov 9, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years:  The employer did not conduct and certify a performance evaluation (driving test) at least once every three years for each employee authorized to operate a powered industrial truck in the workplace.  Abatement certification is required for this item in accordance with 29 CFR 1903.19(c).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Detroit Forming INC's full OSHA safety record →