Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WOLF PACK RENTALS, LLC

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of WOLF PACK RENTALS, LLC in HUNTER HEFLEY 34-7H RIG 733-BRISCOE, BRISCOE, TX 79011 (NAICS 213112). OSHA activity number 339067555.

Watch Wolf Pack Rentals, LLC — free Get an email when a new federal OSHA severe-injury report for Wolf Pack Rentals, LLC is published. One employer, no account, unsubscribe in one click.
Site address
HUNTER HEFLEY 34-7H RIG 733-BRISCOE
City
BRISCOE
State
TX
ZIP
79011
Mailing
8811 COUNTY ROAD 14, BRISCOE, TX 79011
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
15
Ownership type
A

4 citations on file for this inspection.

1910.303 B01

Serious Gravity 5 3 instances 15 exposed
Issued
Abate by
Penalty
Initial $3443.00 · Current $3443.00
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):    MOBILE HOME/OFFICES: On or about March 7, 2013, the employer did not ensure that extension cords powering 110 volt (nominal) equipment such as, but not limited to, sump pumps were inspected and taken out of service when a defect or damage was observed. Employees were exposed to hazards associated with electrical shock, burns and arcing.
Recent events (3)
  • — J (S) $3443
  • — C (S) $3443
  • — Z (S) $3443

1910.304 B03 II A

Serious Gravity 5 3 instances 15 exposed
Issued
Abate by
Penalty
Initial $3443.00 · Current $0.00 Reduced
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15, 20 and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel did not have ground-fault circuit-interrupter protection for personnel.    MOBILE HOME/OFFICES: On or about March 7, 2013, the employer did not ensure that outlets powering equipment in wet locations were equipped with ground fault-circuit interrupters. Employees working with damaged extension cords were exposed to hazards associated with electrical shock, burns and arcing.
Recent events (3)
  • — J (S) $0
  • — C (S) $3443
  • — Z (S) $3443

1910.303 F02

Other-than-serious 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $3443.00 · Current $2410.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident     MOBILE HOME/OFFICES: On or about March 7, 2013, the employer did not ensure that all circuit breakers 110-220 volt (nominal) were marked to indicate their purposes. Not being able to shut off the electrical power to a piece of machinery or equipment in the event of an emergency exposed employees to hazards associated with electrical shock, burns and arcing.
Recent events (3)
  • — J (O) $2410
  • — C (S) $3443
  • — Z (S) $3443

1910.304 G05

Other-than-serious 3 instances 15 exposed
Issued
Abate by
Penalty
Initial $3443.00 · Current $2410.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:     On or about March 7, 2013, the employer did not ensure that mobile home/office trailers were grounded. Employees were exposed to hazards associated with electrical shock, burns and arcing.
Recent events (3)
  • — J (O) $2410
  • — C (S) $3443
  • — Z (S) $3443

View WOLF PACK RENTALS, LLC's full OSHA safety record →

RNWBL

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339067555.