NEWARK, OH ·
OSHA Inspection: J.A. JANES, INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of J.A. JANES, INC. in 349 EAST MAIN STREET, NEWARK, OH 43055 (NAICS 445110). OSHA activity number 339071359.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- J.A. JANES, INC.
- Site address
- 349 EAST MAIN STREET
- City
- NEWARK
- State
- OH
- ZIP
- 43055
- Mailing
- 633 CHARLESTON PIKE, CHILLICOTHE, OH 45601
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 85
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.303 G02 I
- Issued
- Jul 12, 2013
- Penalty
- Initial $2,380 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures. a. In the compressor room where employees check refrigeration equipment, the meat prep electrical door was open, thereby exposing employees to a contact hazard. b. In the compressor room where employees check refrigeration equipment, the ice cream electrical door was open, thereby exposing employees to a contact hazard. c. In the compressor room where employees check refrigeration equipment, the walk in freezer electrical door was open, thereby exposing employees to a contact hazard. d. In the compressor room where employees check refrigeration equipment, the 24 foot M/D dairy electrical door was open, thereby exposing employees to a contact hazard. e. In the compressor room where employees check refrigeration equipment, the 24 foot fresh meat electrical door was open, thereby exposing employees to a contact hazard. f. In the compressor room where employees check refrigeration equipment, the 24 foot end cap electrical door was open, thereby exposing employees to a contact hazard. g. In the compressor room where employees check refrigeration equipment, the 24 foot frozen meat electrical door was open, thereby exposing employees to a contact hazard. h. In the compressor room where employees check refrigeration equipment, the frozen rear end cap electrical door was open, thereby exposing employees to a contact hazard. I. In the compressor room where employees check refrigeration equipment, the 36 foot produce electrical door was open, thereby exposing employees to a contact hazard. j. In the compressor room where employees check refrigeration equipment, the smoked meat electrical door was open, thereby exposing employees to a contact hazard. k. In the compressor room where employees check refrigeration equipment, the electrical cover for the thermostat control, on the north wall behind the door, was off, thereby exposing employees to a contact hazard. l. In the compressor room where employees check refrigeration equipment, the electrical cover for the thermostat control, on the north wall above the defrost controls, was off, thereby exposing employees to a contact hazard.
Recent events (2)
- · I (S) $1428
- · Z (S) $2380
1910.305 B01 I
- Issued
- Jul 12, 2013
- Abate by
- Aug 1, 2013
- Penalty
- Initial $2,380 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. a. In the compressor room where employees check refrigeration equipment, wiring was exposed to the sharp edge of the metal clad cable at the 36 foot produce compressor panel, thereby exposing the employee to a contact hazard.
Recent events (2)
- · I (S) $1428
- · Z (S) $2380
1910.305 B01 II
- Issued
- Jul 12, 2013
- Abate by
- Aug 1, 2013
- Penalty
- Initial $2,380 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a. On the north wall of the compressor room where employees check refrigeration equipment, circuit panel RA had an unused opening of 2.5 x 3 inches, thereby exposing employees to a contact hazard. b. In the compressor room where employees check refrigeration equipment, the panel for the 24 foot dairy case had an unused opening of 2.5 x 2.5 inches, thereby exposing employees to a contact hazard. c. In the compressor room where employees check refrigeration equipment, the junction box for the fresh meat case had an unused opening of 1inch, thereby exposing employees to a contact hazard. d. In the compressor room where employees check refrigeration equipment, the panel for the 36 foot produce case had two unused opening of 1inch, thereby exposing employees to a contact hazard. e. In the compressor room where employees check refrigeration equipment, the panel for the 24 foot frozen meat case had an unused opening of 1 inch, thereby exposing employees to a contact hazard. f. In the compressor room where employees check refrigeration equipment, the switch panel for the 24 foot frozen meat case had an unused opening of 1.5 inches, thereby exposing employees to a contact hazard.
Recent events (2)
- · I (S) $1428
- · Z (S) $2380
1910.332 B02
- Issued
- Jul 12, 2013
- Abate by
- Aug 16, 2013
- Penalty
- Initial $2,380 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.332(b)(2): Additional requirements for unqualified persons. Employees who are covered by paragraph (a) of this section but who are not qualified persons shall also be trained in and familiar with any electrically related safety practices not specifically addressed by 1910.331 through 1910.335 but which are necessary for their safety. a. In the compressor room where an employee was required to open live electrical boxes and check live circuit breakers and timers, the employee as not trained in electrical safety-related work practices, thereby exposing the employee to a contact hazard.
Recent events (2)
- · I (S) $1428
- · Z (S) $2380
1910.335 A01 I
- Issued
- Jul 12, 2013
- Abate by
- Aug 16, 2013
- Penalty
- Initial $2,380 · Current $1,428 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed. Note: Personal protective equipment requirements are contained in subpart I of this part. a. In the compressor room of the store where employees were required to troubleshoot live electrical equipment, personal protective equipment was not provided or used, thereby exposing employees to a contact hazard.
Recent events (2)
- · I (S) $1428
- · Z (S) $2380
More inspections in this industry (NAICS 445110)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339071359.