On , OSHA opened a planned safety inspection of ADRIAN CARRIERS, INC. in 1001 1ST AVE E, MILAN, IL 61264 (NAICS 484121). OSHA activity number 339087066.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ADRIAN CARRIERS, INC.
- Site address
- 1001 1ST AVE E
- City
- MILAN
- State
- IL
- ZIP
- 61264
- Mailing
- PO BOX 20, MILAN, IL 61264
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 484121
- Employees
- 100
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.305 B01
- Issued
- Sep 11, 2013
- Penalty
- Initial $3,600 · Current $3,600
General-duty citation text
29 CFR 1910.305(b)(1): Unused openings in boxes, cabinets, or fittings were not effectively closed: Employees were exposed to electrical shock hazard because an outlet attached to a shop table in the truck maintenance area was missing the side knock-outs.
Recent events (2)
- · I (S) $3600
- · Z (S) $3600
1910.305 G01 IV A
- Issued
- Sep 11, 2013
- Penalty
- Initial $3,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used in lieu of fixed wiring of a structure: Employees were exposed to electrical and fire hazards because flexible cords were used as permanent wiring to provide power to outlets being used on shop tables.
Recent events (2)
- · I (S) $0
- · Z (S) $3600
1910.305 G02 III
- Issued
- Sep 11, 2013
- Penalty
- Initial $3,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: Employees working in the shop were exposed to electrical and fire hazards because a flexible cord used to provide power to outlets was damaged near the plug.
Recent events (2)
- · I (S) $0
- · Z (S) $3600
1910.178 L06
- Issued
- Sep 11, 2013
- Abate by
- Oct 7, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l): Employees operate powered industrial trucks inside and outside of the facility, and the employer did not certify that each employee had received training and evaluation as specified by 1910.178(l). This certification would include: a. Name of the operator, b. Date of the training, c. Date of the evaluation, and d. Identity of the person(s) performing the training or evaluation.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.305 B02 I
- Issued
- Sep 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Employees were exposed to electrical shick hazards because: a. The outlet used to power the vending machine in the front office was broken and did not fully cover the outlet box. b. The outlet used to power the cellular phone charger in the shop office was broken and did not fully cover the outlet box.