OSHA Inspection: NORTH AMERICA HOGANAS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NORTH AMERICA HOGANAS, INC. in 5950 PACKARD ROAD, NIAGARA FALLS, NY 14304 (NAICS 331110). OSHA activity number 339098733.

Watch North America Hoganas, INC. — free Get an email when a new federal OSHA severe-injury report for North America Hoganas, INC. is published. One employer, no account, unsubscribe in one click.
Site address
5950 PACKARD ROAD
City
NIAGARA FALLS
State
NY
ZIP
14304
Mailing
5950 PACKARD ROAD, NIAGARA FALLS, NY 14304
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331110
Employees
42
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 3 instances 8 exposed
Issued
Penalty
Initial $5000.00 · Current $5000.00
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to potential explosive levels of hydrogen gas.      a) On or about 6/5/13 at #10 Furnace; calibration of the hydrogen gas sensors for the Beacon 800 Gas monitor was not conducted within the frequency described in the Operator's Manual.   Since the installation of the sensors in June 2012 no calibration was performed.      b) On or about 6/5/13 at # 7 Furnace; calibration of the hydrogen gas sensors for the Beacon 800 Gas monitor was not conducted within the frequency described in the Operator's Manual.  Since the installation of the sensors on December 23, 2012 no calibration was performed.      c) On or about 6/5/13 at #9 Furnace; calibration of the hydrogen gas sensors for the Beacon 800 Gas monitor was not conducted within the frequency described in the Operator's Manual.  Since the installation of the sensors on February, 8 2013, no calibration was performed.      Among other methods, several feasible and acceptable abatement methods to correct this hazard include; following the Calibration Frequency described in the Beacon 800 Gas Monitor Operator's Manual.      National Fire Protection Association, NFPA 654 Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids, 2005 revision.     Page 12 of the Operators Manual states:  Although there is no particular calibration frequency that is correct for all applications, a calibration frequency of every 3 to 6 months is adequate for most hydrogen transmitter applications.  Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every three months.      Section 12.1.1; An inspection, testing, and maintenance program shall be developed and implemented to ensure that the fire and explosion protection systems and related process controls and equipment perform as designed.      No Abatement Documentation Required
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5000

1910.305 B01 II

Other-than-serious 1 instance 8 exposed
Issued
Penalty
Initial $3400.00 · Current $0.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    a) On or about 6/5/13 at # 7 furnace; the end of the conduit on the junction box, located at the discharge of the furnace, was open.       No Abatement Certification Required
Recent events (2)
  • — I (O) $0
  • — Z (S) $3400

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339098733.