AMMON, ID ·
OSHA Inspection: CLUB, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of CLUB, INC. in 1904 DAKOTA LANE, AMMON, ID 83406 (NAICS 624190). OSHA activity number 339104572.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CLUB, INC.
- Site address
- 1904 DAKOTA LANE
- City
- AMMON
- State
- ID
- ZIP
- 83406
- Mailing
- 2001 S WOODRUFF SUITE #6, IDAHO FALLS, ID 83404
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 624190
- Employees
- 6
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.157 E
- Issued
- Jul 23, 2013
- Abate by
- Aug 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e): Portable fire extinguishers were not visually inspected at least monthly: a) On or about June 5, 2013, and at times prior thereto, the Kidde fire extinguishers available at the establishment had no evidence of monthly inspections. NOTE: Abatement certification is required for this item.
Recent events (1)
- · Z (O) $0
1910.157 E04
- Issued
- Jul 23, 2013
- Abate by
- Aug 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(4): Stored pressure dry chemical portable fire extinguishers that require a 12 year hydrostatic test were not emptied and subjected to applicable maintenance procedures every 6 years: a) On or about June 5, 2013, the Kidde Fire Away 240 extinguisher in the laundry room had not undergone hydrostatic applicable maintenance since 2003. NOTE: Abatement certification is required for this item.
Recent events (1)
- · Z (O) $0
1910.303 B02
- Issued
- Jul 23, 2013
- Abate by
- Aug 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Kitchen Area: On or about June 5, 2013, and at times prior thereto, the 110 volt 2-receptacle outlet located below the paper towel dispenser next to the sink on the counter between the kitchen and the meeting area did not have the grounded electrode connected, i.e. open neutral. NOTE: Abatement certification is required for this item.
Recent events (1)
- · Z (O) $0
More inspections in this industry (NAICS 624190)
More inspections in ID
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339104572.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.