OSHA Inspection: THE FIRST BAPTIST CHURCH OF HARTFORD

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of THE FIRST BAPTIST CHURCH OF HARTFORD in 1151 BLUE HILLS AVE., BLOOMFIELD, CT 06002 (NAICS 813110). OSHA activity number 339113052.

Watch THE First Baptist Church OF Hartford — free Get an email when a new federal OSHA severe-injury report for THE First Baptist Church OF Hartford is published. One employer, no account, unsubscribe in one click.
Site address
1151 BLUE HILLS AVE.
City
BLOOMFIELD
State
CT
ZIP
06002
Mailing
1151 BLUE HILLS AVE., BLOOMFIELD, CT 06002
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
813110
Employees
28
Ownership type
A

7 citations on file for this inspection.

1910.23 C02

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $2450.00 Reduced
29 CFR 1910.23(c)(2): Runways four feet or more above floor or ground level were not guarded by standard railings (or the equivalent):    On, or about, July 5, 2013, standard railings or another effective fall protection system was not provided to an electrician who accessed a platform system laid on the suspended ceiling of the sanctuary to change lightbulbs.  The suspended ceiling had not been designed to bear weight.    Abatement Note:  In a report dated October 18, 2013, a structural engineer determined that the suspended ceiling was not designed to hold the weight of platforms and a person and all maintenance activities had to be conducted from below or an engineered platform system needed to be installed.
Recent events (3)
  • — F (S) $2450
  • — C (S) $4900
  • — Z (S) $4900

1910.37 A03

Serious Gravity 1 2 instances 10 exposed
Issued
Penalty
Initial $2100.00 · Current $1050.00 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    Facility:  On, or about, June 12, 2013, the following exit stairwells were used for storage:    A.  Stairwell 2.  B.  Stairwell 3.
Recent events (3)
  • — F (S) $1050
  • — C (S) $2100
  • — Z (S) $2100

1910.303 B07 IV

Serious Gravity 5 1 instance 8 exposed
Issued
Penalty
Initial $3500.00 · Current $1750.00 Reduced
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemcial action or overheating.       Kitchen Electrical/Supply Room:  On, or about, June 12, 2013, water had backed up into an electrical raceway from a water leak at the outdoor marquis sign electrical box.  The raceway was draining into a funnel and was not provided with a cover.
Recent events (3)
  • — F (S) $1750
  • — C (S) $3500
  • — Z (S) $3500

1910.303 G01 I C

Serious Gravity 1 2 instances 8 exposed
Issued
Penalty
Initial $2100.00 · Current $1050.00 Reduced
29 CFR 1910.303(g)(1)(i)(C):  Other equipment associated with the electrical installation and located above or below the electric equipment extended more than 153 mm (6 in.) beyond the front of the electric equipment:    A.  Main Electrical Room:  On, or about, June 12, 2013, a Square D transformer was located in the working space for circuit breaker panel LV-1-1.    B.  Kitchen Electrical/Supply Room:  On, or about, June 12, 2013, a Square D transformer was located in the working space for circuit breaker panel LV2-1.
Recent events (3)
  • — F (S) $1050
  • — C (S) $2100
  • — Z (S) $2100

1910.304 F01 IV

Serious Gravity 1 5 instances 8 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:  On, or about, June 12, 2013, items were stored in front of the following electrical panels:  A.  Main Electrical Room:  1.  Panel SL. 2.  Panel HV-1 3.  Panel LV-1.  B.  Kitchen Electrical/Supply Room: 1.  Panel HV2. 2.  Panel LV2.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 3 instances 8 exposed
Issued
Penalty
Initial $3500.00 · Current $1750.00 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    A.  Main Electrical Room:  On, or about, June 12, 2013, the internal shields were not installed in the two Tork timers used to control light fixtures at the facility.     B.  Kitchen Electrical/Supply Room:  On, or about, June 12, 2013, the internal shield was not installed in the Tork timer unit used to control the outdoor sign.
Recent events (3)
  • — F (S) $1750
  • — C (S) $3500
  • — Z (S) $3500

1910.37 B02

Other-than-serious 2 instances 10 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  Main Electrical Room:  On, or about, June 12, 2013, the doors leading from the room were not provided with exit signs.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0