OSHA Inspection: MASTERBRAND CABINETS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MASTERBRAND CABINETS, INC. in 101 EAST PARKWAY, TALLADEGA, AL 35160 (NAICS 337110). OSHA activity number 339133407.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Masterbrand Cabinets, INC. for free Get an email when a new federal OSHA severe-injury report for Masterbrand Cabinets, INC. is published. One employer, no account, unsubscribe in one click.
Site address
101 EAST PARKWAY
City
TALLADEGA
State
AL
ZIP
35160
Mailing
101 EAST PARKWAY, TALLADEGA, AL 35160
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
Employees
250
Ownership type
Private (A)

5 citations on file for this inspection.

1910.23 E02

Serious Gravity 5 2 instances 6 exposed
Issued
Sep 23, 2013
Abate by
Oct 3, 2013
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.23(e)(2): Stair rails did not consist of a top rail, intermediate rail and/or posts, with the vertical height not more than 34 inches (86.36 cm) nor less than 30 inches (76.2 cm) from upper surface of top rail to surface of tread in line with face of riser at forward edge of tread:     (a) On or about 06/20/13 - Building 6, Catwalk at Line #1, the stairs on both sides of the catwalk did not have intermediate rails installed.
Recent events (2)
  • · I (S) $1700
  • · Z (S) $3400

1910.147 C06 I

Serious Gravity 5 4 instances 7 exposed
Issued
Sep 23, 2013
Abate by
Oct 3, 2013
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    (a) On or about 06/20/13 - Facility, periodic inspections of the energy control procedures had not been conducted for employees performing servicing and maintenance of equipment such as, but not limited to, the Ritter drill, Pistorius notcher, Extrema profiler, and other woodworking equipment.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.212 A01

Serious Gravity 5 3 instances 8 exposed
Issued
Sep 23, 2013
Abate by
Oct 3, 2013
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    (a) On or about 06/30/13 - Maintenance shop, the Index milling and drilling machine did not have a spindle guard installed.    (b) On or about 06/30/13 - Maintenance shop, the Manhattan pedestal drill press did not have a chuck guard installed.    (c) On or about 06/30/13 - Maintenance shop, the MSC band saw did not have a guard installed for the unused portion of blade below the work table.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.303 B07 IV

Serious Gravity 10 4 instances 5 exposed
Issued
Sep 23, 2013
Abate by
Oct 3, 2013
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    (a) On or about 06/20/13 - Building 6, East wall, the 480-volt disconnect had a damaged box and control handle.    (b) On or about 06/20/13 - Building 5, Ritter drill, the 480-volt disconnect had a damaged control handle.    (c) On or about 06/20/13 - Building 5, Pistorius notcher, the 480-volt disconnect had a damaged control handle.    (d) On or about 06/20/13 - Building 5, Extrema profiler, the 480-volt disconnect had a damaged control handle.
Recent events (2)
  • · I (S) $3500
  • · Z (S) $7000

1910.303 G01

Serious Gravity 1 2 instances 4 exposed
Issued
Sep 23, 2013
Abate by
Oct 3, 2013
Penalty
Initial $2,550 · Current $1,275 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:    (a) On or about 06/20/13 - Building 6, 6L & 6K, the 220-volt electrical panels and 480-volt transformer were blocked by several pallets of stacked materials.     (b) On or about 06/20/13 - Building 6, Holding area, the 220-volt electrical panels were blocked by several pallets of stacked materials.
Recent events (2)
  • · I (S) $1275
  • · Z (S) $2550

View Masterbrand Cabinets, INC.'s full OSHA safety record →