CHICAGO, IL ·
OSHA Inspection: KINGDOM CHEVROLET
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of KINGDOM CHEVROLET in 6603 S. WESTERN AVE., CHICAGO, IL 60636 (NAICS 441110). OSHA activity number 339134272.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KINGDOM CHEVROLET
- Site address
- 6603 S. WESTERN AVE.
- City
- CHICAGO
- State
- IL
- ZIP
- 60636
- Mailing
- 6603 S. WESTERN AVE., CHICAGO, IL 60636
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 441110
- Employees
- 85
- Ownership type
- Private (A)
Citations
10 citations on file for this inspection.
1910.22 A01
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $4,200 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, and service rooms shall be kept clean and orderly and in a sanitary condition. a. Shop Area, Bay 2 - On or about May 28, 2013, stairwell located on ground floor leading to second level storage area where electrical panel boxes are located at southwest corner of facility was cluttered with electrical wire-harnesses, plastic hoses, rubber fittings, windshield washer bottles, rubber squeezee, and empty boxes blocking passageway leading to second level. Thereby exposing employees to slip, trip, and fall hazard(s).
Recent events (2)
- · I (S) $2100
- · Z (S) $4200
1910.22 A02
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(2): The floor of every workroom shall be maintained in a clean and, so far as possible, a dry condition. Where wet processes are used, drainage shall be maintained, and false floors, platforms, mats, or other dry standing places should be provided where practicable. a. Shop Area, Bay 2- On or about 28 May 2013, employee's were required to work in a puddle of standing rainwater covering a portion of the automotive bay located along the north wall at southwest corner of facility. Thereby exposing employees to slip, trip, and fall hazard(s).
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 B02
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $3,500 · Current $1,750 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. a. Shop Area Level 2- On or about May 28, 2013, employee's are required to access an electrical panel box attached to east wall, located on southwest corner of facility. This panel had been modified, the original panel box cover had been removed and replaced with a fabricated sheet metal cover, which was then attached to front of panel box with four screw(s) and four nut(s). Black masking tape was also applied to top, bottom and sides of box to help keep panel door shut. Thereby exposing employees to shock, electrocution, arch flash and fire hazard(s).
Recent events (2)
- · I (S) $1750
- · Z (S) $3500
1910.303 F02
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident. a. Shop Area Level 2- On or about May 28, 2013, employee's were required to access an electrical panel box that was not properly marked to indicate facilities services, feeders, and branch circuits throughout shop area. The panel box is attached to east wall on southwest corner of facility. Thereby exposing employees to shock, electrocution, and fire hazard(s).
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 G01
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. a. Shop Area Level 2 - On or about May 28, 2013, employees were required to access an obstructed panel box located at southwest corner of facility. The panel was obstructed and blocked by wire harnesses, plastic hoses, rubber fittings, windshield washer bottles, empty tray(s) and other debris. Thereby exposing employees to shock, electrocution, and fire hazard(s).
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.304 A02
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $3,500 · Current $1,750 Reduced
General-duty citation text
29 CFR 1910.304(a)(2): Polarity of connections. No grounded conductor may be attached to any terminal or lead so as to reverse designated polarity. a. Shop Area, Bay Area 1- On or about May 28, 2013, employees were required to use a dual electrical outlet with reversed polarity at their workstation. Thereby exposing employees to shock, electrocution and fire hazard(s).
Recent events (2)
- · I (S) $1750
- · Z (S) $3500
1910.304 B02 I
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(2)(i): Receptacles installed on 15- and 20-ampere branch circuits shall be of the grounding type except as permitted for replacement receptacles in paragraph (b)(2)(iv) of this section. Grounding-type receptacles shall be installed only on circuits of the voltage class and current for which they are rated, except as provided in Table S-4 and Table S-5. Bay 1- On or about May 28, 2013, employees were required to use outlets that had broken ground pins lodged inside of them. Thereby exposing employees to shock and electrocution hazard(s).
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 B01 I
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $3,500 · Current $1,750 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. a. Ground Floor Southeast - On or about May 28, 2013 employees were required to use cutout box's with exposed live wires. Thereby exposing employees to shock and electrocution hazard.
Recent events (2)
- · I (S) $1750
- · Z (S) $3500
1910.305 B02 I
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. a. Ground Floor Southeast Corner- On or about May 28, 2013, employees had access to renovation site where there was an electrical outlet box with exposed conductors (wires) protruding outside the wall that was not installed. Thereby exposing employees to shock and electrocution hazard.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.157 C01
- Issued
- Jul 24, 2013
- Abate by
- Aug 19, 2013
- Penalty
- Initial $700 · Current $350 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury. Level 2- On or about May 28, 2013, employees were required to access fire extinguisher located by electrical panel box at southwest corner of facility that was blocked by electrical wireharnesses, plastic hoses, rubber fittings, windshield washer bottles, and a empty storage box. Thereby exposing employees to fire hazard.
Recent events (2)
- · I (O) $350
- · Z (O) $700
More inspections at Kingdom Chevrolet
View Kingdom Chevrolet's full OSHA safety record →
More inspections in this industry (NAICS 441110)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339134272.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.