BRONX, NY —
OSHA Inspection: CONWAY STORES
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CONWAY STORES in 2952 THIRD AVENUE, BRONX, NY 10455 (NAICS 448140). OSHA activity number 339135014.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONWAY STORES
- Site address
- 2952 THIRD AVENUE
- City
- BRONX
- State
- NY
- ZIP
- 10455
- Mailing
- 2952 THIRD AVENUE, BRONX, NY 10455
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 448140
- Employees
- 40
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.23 E06
- Issued
- Nov 6, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $4,000 · Current $4,000
General-duty citation text
29 CFR 1910.23(e)(6): 29 CFR 1910.23(e)(6): Handrails were not installed with a minimum of three inches of clearance between the handrail and another object to allow grasping of the handrail: On or about 6/21/13 Location: 2952 Third Avenue, Bronx, NY 10455 a) The handrails on the stairs to the basement were attached directly to the walls with no space between the handrail and the wall.
Recent events (3)
- — C (S) $4000
- — F (S) $4000
- — Z (S) $4000
1910.37 B05
- Issued
- Nov 6, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $3,000 · Current $3,000
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use: On or about 6/21/13 Location: Recieving area, 2952 Third Avenue, Bronx, NY 01455 a) Two loading dock doors which could be mistaken for emergency exits were not were not marked "Not an Exit".
Recent events (3)
- — C (S) $3000
- — F (S) $3000
- — Z (S) $3000
1910.303 B02
- Issued
- Nov 6, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about 6/21/13 Location: 2952 Third Avenue, Bronx, NY 10455 a) Numerous circuit breakers in panels located in the basement, main floor, shoe and lingerie storage areas had tape placed over the breakers. The tape prevents the breaker from operating/tripping properly in the manner it was designed and possible overheating and fire.
Recent events (3)
- — C (S) $5000
- — F (S) $5000
- — Z (S) $5000
1910.303 F
- Issued
- Nov 6, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $3,000 · Current $3,000
General-duty citation text
29 CFR 1910.303(f): Each service, feeder and branch circuit, at its disconnecting means or over current device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about 6/21/13 Location 2952 Third Avenue, Bronx, NY 10455 a) The individual breakers in the circuit breaker panels in the lingerie storage room and basement panel # 16 were not labeled or marked to indicate their purpose.
Recent events (3)
- — C (S) $3000
- — F (S) $3000
- — Z (S) $3000
1910.303 G01
- Issued
- Nov 6, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $3,000 · Current $3,000
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. On or about 6/21/2013 Location: 2952 Third Avenue, Bronx, NY 10455 a) 120 volt electrical circuit breaker panels in the basement and shoe storage room were blocked with boxes of stored merchendise.
Recent events (3)
- — C (S) $3000
- — F (S) $3000
- — Z (S) $3000
1910.305 B01 II
- Issued
- Nov 6, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about 6/21/13 Location: 2952 Third Avenue, Bronx, NY 10455 a) Lingerie stock room b) Basement panel # 16 a) The 120 volt circuit breaker panel had two open breaker positions exposing live electrical buses and wiring. b) The 120 volt circuit breaker panel had two open breaker positions exposing live electrical buses and wiring.
Recent events (3)
- — C (S) $5000
- — F (S) $5000
- — Z (S) $5000
1910.305 G01 IV A
- Issued
- Nov 6, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about 6/21/13 Location: receiving area, 2952 Third Avenue, Bronx NY a) Three orange extension cords were used in place of permanent building wiring to provide power to lighting in the area. The cords were run over and attached to electrical conduit, piping and steel shelving members.
Recent events (3)
- — C (S) $5000
- — F (S) $5000
- — Z (S) $5000
More inspections in this industry (NAICS 448140)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339135014.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.