Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: SSC SAMOA SPORTS CENTER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SSC SAMOA SPORTS CENTER in AIRPORT ROAD, TAFUNA, PAGO PAGO, AS 96799 (NAICS 238190). OSHA activity number 339154460.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch SSC Samoa Sports Center for free Get an email when a new federal OSHA severe-injury report for SSC Samoa Sports Center is published. One employer, no account, unsubscribe in one click.
Site address
AIRPORT ROAD, TAFUNA
City
PAGO PAGO
State
AS
ZIP
96799
Mailing
P.O. BOX 580, PAGO PAGO, AS 96799
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238190
Employees
25
Ownership type
Private (A)

3 citations on file for this inspection.

1910.305 G01 III

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 19, 2013
Abate by
Oct 8, 2013
Penalty
Initial $1,600 · Current $1,000 Reduced
29 CFR 1910.305(g)(1)(iii): Flexible cords were not equipped with an attachment plug and energized from an approved receptacle outlet:    This violation was observed on June 18, 2013; where an electrical cord powering a welder was hard wired into a circuit breaker box.
Recent events (2)
  • · I (S) $1000
  • · Z (S) $1600

1926.403 B01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 19, 2013
Abate by
Oct 8, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.403(b)(1)(i): Safety of equipment was not determined on the basis of suitability of the equipment for an identified purpose as evidenced by listing, labeling, or certification for that identified purpose.  This violation was discovered on June 18, 2013; where a non UL approved cord assembly was used to power a welder.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1926.405 D

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 19, 2013
Abate by
Oct 8, 2013
Penalty
Initial $1,600 · Current $1,000 Reduced
29 CFR 1926.405(d): Switchboards and panelboards. Switchboards that have any exposed live parts shall be located in permanently dry locations and accessible only to qualified persons. Panelboards shall be mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. However, panelboards other than the dead front externally-operable type are permitted where accessible only to qualified persons. Exposed blades of knife switches shall be dead when open.     This violation was observed on June 18, 2013; where a live electrical panel board was open and exposed live electrical parts.
Recent events (2)
  • · I (S) $1000
  • · Z (S) $1600

View SSC Samoa Sports Center's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339154460.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.