ST JOHN, VI ·
OSHA Inspection: U.S. CUSTOMS AND BORDER PROTECTION-PORT OF ST JOHN
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. CUSTOMS AND BORDER PROTECTION-PORT OF ST JOHN in CRUZ BAY CREEK BULKHEAD, ST JOHN, VI 00830 (NAICS 928110). OSHA activity number 339160905.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. CUSTOMS AND BORDER PROTECTION-PORT OF ST JOHN
- Site address
- CRUZ BAY CREEK BULKHEAD
- City
- ST JOHN
- State
- VI
- ZIP
- 00830
- Mailing
- CRUZ BAY CREEK BULKHEAD, ST JOHN, VI 00830
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 4
- Ownership type
- Federal government (D)
Citations
5 citations on file for this inspection.
1910.303 B02
- Issued
- Sep 17, 2013
- Abate by
- Oct 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling: a) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the cargo inspection area, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle. b) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI in the cargo inspection area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle. c) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI in the supervisor's office area, a relocatable power tap was not directly connected to a permanently installed branch circuit receptacle. d) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the kitchen area, a ground-fault circuit interrupter was not installed in all 125-volt, single phase, 15-and 20-ampere receptacles installed within 6 feet or 1.8 meters of the outside edge of a sink. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- Sep 17, 2013
- Abate by
- Oct 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear: a) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the breakroom area, an electrical outlet box was not covered. b) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the primary inspection area, an electrical outlet box was not covered. c) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the primary inspection, an electrical junction box was not covered. d) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the secondary/agriculture area, an electrical outlet box was not covered. e) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the hallway area, an electrical junction box was not covered. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV C
- Issued
- Sep 17, 2013
- Abate by
- Oct 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through doorways, windows, or similar openings: On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the laboratory/bathroom area, the flexible cord of the electrical hand dryer was run through a hole on the wall. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- · Z (S) $0
1910.305 G02 III
- Issued
- Sep 17, 2013
- Abate by
- Oct 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about 06/27/13, at Cruz Bay Creek Bulkhead, VI, in the water pump area, the outer insulation of the electrical cord was coming off due to the lack of strain relief. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- · Z (S) $0
1910.157 C01
- Issued
- Sep 17, 2013
- Abate by
- Oct 11, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury: a) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the cargo inspection area, two portable fire extinguishers were not mounted. b) On or about 06/27/13, at Cruz Bay Creek Bulkhead, St John, VI, in the primary inspection area, a portable fire extinguisher was not mounted. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- · Z (O) $0
More inspections in this industry (NAICS 928110)
More inspections in VI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339160905.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.