Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: PHOENIX INDIAN MEDICAL CENTER-ENGINEERING

Unprogrammed Other inspection · Health discipline

On , OSHA opened an unprogrammed Other health inspection of PHOENIX INDIAN MEDICAL CENTER-ENGINEERING in 4212 N 16TH STREET, PHOENIX, AZ 85016 (NAICS 561210). OSHA activity number 339169377.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Phoenix Indian Medical Center-Engineering — free Get an email when a new federal OSHA severe-injury report for Phoenix Indian Medical Center-Engineering is published. One employer, no account, unsubscribe in one click.
Site address
4212 N 16TH STREET
City
PHOENIX
State
AZ
ZIP
85016
Mailing
4212 N 16TH STREET, PHOENIX, AZ 85016
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
60
Ownership type
D

4 citations on file for this inspection.

1910.151 C

Serious Gravity 1 1 instance 4 exposed
Issued
Sep 30, 2013
Abate by
Oct 18, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  (a) Boiler Plant, Phoenix Indian Medical Center: On or about 27 June 2013 and at times prior thereto, the installation of a ball valve, in line with the water supply to the eyewash, delayed activation during emergency use. Employees in the plant are exposed to the corrosive product "3D TRASAR 3DT289", a corrosion/scale inhibitor for the cooling water, containing phosphoric acid.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 1 1 instance 4 exposed
Issued
Sep 30, 2013
Abate by
Oct 10, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:  (a) Welding Shop, Phoenix Indian Medical Center: On or about 27 June 2013 and at times prior thereto, a cylinder of oxygen and a cylinder of acetylene were stored side-by-side on a welding cart.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 B04

Serious Gravity 1 1 instance 4 exposed
Issued
Sep 30, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(4): Outlet devices did not have an ampere rating greater than the load to be served:  (a) Housekeeping Break Room, Phoenix Indian Medical Center: On or about 27 June 2013 and at times prior thereto, high power appliances, a Gibson refrigerator and an Amana microwave oven, were plugged into the Relocatable Power Tap (RPT).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.501 B01

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 30, 2013
Abate by
Oct 15, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.501(b)(1): Each employee on a walking/working surface with an unprotected side or edge which was 6 feet (1.8 m) or more above a lower level was not protected from falling by the use of guardrail systems, safety net systems, or personal fall arrest systems:  (a) Building-North of Dental Clinic, Phoenix Indian Medical Center: On or about 2 July 2013, employees installed a turbine roof vent without having fall protection. The roof was approximate 8 feet, 8 inch above ground level.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Phoenix Indian Medical Center-Engineering's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339169377.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.