Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ADCARE HEALTH SYSTEMS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ADCARE HEALTH SYSTEMS, INC. in 812 OLD EXITER ROAD, CASSVILLE, MO 65625 (NAICS 561499). OSHA activity number 339208449.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Adcare Health Systems, INC. — free Get an email when a new federal OSHA severe-injury report for Adcare Health Systems, INC. is published. One employer, no account, unsubscribe in one click.
Site address
812 OLD EXITER ROAD
City
CASSVILLE
State
MO
ZIP
65625
Mailing
812 OLD EXITER ROAD, CASSVILLE, MO 65625
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561499
Employees
70
Ownership type
A

3 citations on file for this inspection.

1910.303 B07

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 13, 2013
Abate by
Sep 9, 2013
Penalty
Initial $5,100 · Current $3,570 Reduced
29 CFR 1910.303(b)(7:  The employer did not insure that electric equipment was installed in neat and workmanlike manner:   (a)  The conductors providing power to the fluosescent light above the maintenance workbench were connected by wire nuts only, the conductors were not protected from abrasion, and the connection was not contained within an approved box.
Recent events (2)
  • — I (S) $3570
  • — Z (S) $5100

1910.305 B01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 13, 2013
Abate by
Sep 9, 2013
Penalty
Initial $5,100 · Current $3,570 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:  (a) The cable providing power to the In Sink Erator, model SS-200 garbage disposal under the sink in the dishwashing area was not provided with the proper fitting where it went into a box to protect the conductors from abraison.
Recent events (2)
  • — I (S) $3570
  • — Z (S) $5100

1910.305 G01 IV

Serious Gravity 1 1 instance 2 exposed
Issued
Aug 13, 2013
Abate by
Sep 9, 2013
Penalty
Initial $2,550 · Current $1,785 Reduced
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv)   (a) In the maintenance building, above the work bench, a flexible extension cord had been used to power a light in lieu of permanent wiring.
Recent events (2)
  • — I (S) $1785
  • — Z (S) $2550