Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: PARADIGM HEALTHCARE DEVELOPMENT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PARADIGM HEALTHCARE DEVELOPMENT in 80 FERN DRIVE, TORRINGTON, CT 06790 (NAICS 623311). OSHA activity number 339208787.

Watch Paradigm Healthcare Development — free Get an email when a new federal OSHA severe-injury report for Paradigm Healthcare Development is published. One employer, no account, unsubscribe in one click.
Site address
80 FERN DRIVE
City
TORRINGTON
State
CT
ZIP
06790
Mailing
80 FERN DRIVE, TORRINGTON, CT 06790
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623311
Employees
148
Ownership type
A

4 citations on file for this inspection.

1910.37 A04

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $4675.00 · Current $4675.00
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:   A.  On or about August 15, 2013, Basement, Boiler Room:  The emergency fire door from the Boiler Room to an outdoor exit route had been painted shut, preventing it from opening.
Recent events (2)
  • — I (S) $4675
  • — Z (S) $4675

1910.303 G01 I

Serious Gravity 1 1 instance 1 exposed
Issued
Penalty
Initial $2805.00 · Current $2805.00
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less:   A.  On or about August 15, 2013 in the Basement, Electrical Room:  A box of ceiling tiles was stored in the work space in front of electrical panel B-9, which powered downstairs lights, outlets and equipment.
Recent events (2)
  • — I (S) $2805
  • — Z (S) $2805

1910.303 G02 I

Serious Gravity 5 2 instances 1 exposed
Issued
Penalty
Initial $3740.00 · Current $3740.00
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):   On or about August 15, 2013, Basement:  In the following locations, live parts of electrical equipment were not guarded against accidental contact:  A.  Electrical Room:  A Tork timer which controlled the courtyard lights and outsight lights (south) did not have the inner contacts guarded.  B.  Boiler Room:  A 120/24V transformer reset box was missing a cover, exposing energized parts.
Recent events (2)
  • — I (S) $3740
  • — Z (S) $3740

1910.304 G05

Serious Gravity 5 1 instance 148 exposed
Issued
Penalty
Initial $22000.00 · Current $7000.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:      A.  On or about August 15, 2013, Basement:  The Pepsi and snack vending machines were powered through a 2-outlet receptacle which showed an open ground when tested.  Employees were exposed to electric shock hazards.      Marathon Healthcare Center of Torrington, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard, 1910.304(f)(6), which was contained in OSHA inspection number 311759740, Citation Number 1, Item Number 3 and was affirmed as a final order on January 12, 2009, with respect to a workplace located at 80 Fern Drive, Torrington, Connecticut.
Recent events (2)
  • — I (S) $7000
  • — Z (R) $22000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339208787.