Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DEPT OF HOMELAND SECURITY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DEPT OF HOMELAND SECURITY in 9901 S CAGE BLVD, PHARR, TX 78577 (NAICS 928110). OSHA activity number 339214181.

Watch Dept OF Homeland Security — free Get an email when a new federal OSHA severe-injury report for Dept OF Homeland Security is published. One employer, no account, unsubscribe in one click.
Site address
9901 S CAGE BLVD
City
PHARR
State
TX
ZIP
78577
Mailing
9901 S CAGE BLVD SUITE B, PHARR, TX 78577
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
300
Ownership type
D

1 citation on file for this inspection.

1910.303 B01 I

Serious Gravity 10 2 instances 300 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(1)(i): Electrical equipment was not free from recognized hazards likely to cause death or serious physical harm, in that the employer did not ensure that the electrical equipment was suitable for installation and use in conformity with the provisions of this subpart:   At these locations, electrical equipment operating at 120 volts AC, at a height of 38 inches above the floor, was not approved for use in damp locations. Unprotected employees were exposed to shock hazards while engaged in customs and border protection point of entry activities and operating non-approved electrical equipment wet with wind driven rain water:     a. Pharr-Port of EntryPrimary Lanes 1-4: Non approved electrical equipment including but not limited to, wall mounted circuit breaker metal panel boards, light switch metal enclosures, duplex receptacle metal enclosures,  and Computer Processing Units, Monitors, Card Readers, and Mouse Devices.     b. Anzaldua Port of Entry-Primary Lanes 1-4. Non approved electrical equipment including but not limited to, wall mounted circuit breaker metal panel boards, light switch metal enclosures, duplex receptacle metal enclosures, and Computer Processing Units, Monitors, Card Readers, and Mouse Devices.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View DEPT OF HOMELAND SECURITY's full OSHA safety record →