OSHA Inspection: SAFE AIR OF ILLINOIS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SAFE AIR OF ILLINOIS, INC. in 1855 SOUTH 54TH STREET, CICERO, IL 60804 (NAICS 332322). OSHA activity number 339220972.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Safe AIR of Illinois, INC. — free Get an email when a new federal OSHA severe-injury report for Safe AIR of Illinois, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1855 SOUTH 54TH STREET
City
CICERO
State
IL
ZIP
60804
Mailing
1855 SOUTH 54TH STREET, CICERO, IL 60804
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332322
Employees
29
Ownership type
A

11 citations on file for this inspection.

1910.23 C01

Serious Gravity 10 1 instance 3 exposed
Issued
Sep 4, 2013
Abate by
Oct 22, 2013
Penalty
Initial $4,900 · Current $2,450 Reduced
29 CFR 1910.23(c)(1): Every open-sided floor or platform 4 feet or more above adjacent floor or ground level shall be guarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides except where there is entrance to a ramp, stairway, or fixed ladder. The railing shall be provided with a toeboard wherever, beneath the open sides,  a. Loading Dock- On or about July 22, 2013, employees were required to perform work on unguarded elevated surface that was more than four (4) feet in height. Thereby exposing employees to elevated fall hazard(s).
Recent events (2)
  • — I (S) $2450
  • — Z (S) $4900

1910.219 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.219(b)(1): Flywheels. Flywheels located so that any part is seven (7) feet or less above floor or platform shall be guarded in accordance with the requirements of this subparagraph:  a. Ground Floor, Shutter Department- On or about July 22, 2013, employees were required to perform work on an unguarded punch press machine with exposed Flywheel. Thereby exposing employees to caught in, caught on, and amputation hazard(s).
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.217 B07 II

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.217(b)(7)(ii): A red color stop control shall be provided with the clutch/brake control system. Momentary operation of the stop control shall immediately deactivate the clutch and apply the brake. The stop control shall override any other control, and reactuation of the clutch shall require use of the operating (tripping) means which has been selected.  a. Ground Floor, Machine Department- On or about July 22, 2013, employees were required to perform task(s) utilizing a mechanical punch press machine that did not have a functioning emergency stop button. Thereby exposing employees to amputation hazard(s).
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.304 A02

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Abate by
Oct 22, 2013
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.304(a)(2): Polarity of connections. No grounded conductor may be attached to any terminal or lead so as to reverse designated polarity.  a. First Floor, Loading Dock - On or about July  23, 2013, employees were required to use a dual electrical outlet with reversed and open ground polarity at workstation thereby; exposing employees to shock, electrocution and fire hazard(s).
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.  a. First Floor, Machine Department- On or about July 22, 2013, employees were required to use outlet(s) with uncovered openings. Wires inside of exposed outlet were live. Thereby exposing employees to shock and electrocution hazard(s).
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.305 B02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.  a. Gound Floor, Machine Department- On or about July 22, 2013, employees had access to electrical outlet box with exposed conductors (wires) that were not effectively closed. Thereby exposing employees to shock and electrocution hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.  a. Ground Floor, Welding area, southern end of production plant- On or about July 22, 2013 employees were exposed to contact with exposed (live) electrical wiring that had worn away from the base of disconnect box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles may have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 2.44 m (8.0 ft) above the floor may have exposed terminals.  a. Ground Floor, Machine Department- On or about July 13, 2013, employees had access to exposed wires inside of suspended and dangling light fixture(s) that were separated from their housing unit(s). Thereby exposing employees to shock and electrocution hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J03 I

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 4, 2013
Abate by
Oct 22, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(3)(i): Appliances may have no live parts normally exposed to contact other than parts functioning as open-resistance heating elements, such as the heating elements of a toaster, which are necessarily exposed.  a. Machine Shop- On or about July 22, 2013, Employees were exposed to (live) electrical wires on the rear of an upright industrial  floor fan that was positioned in front of pressbrake machine. Thereby exposing employees to shock and electrocution hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 A03

Other-than-serious 1 instance 29 exposed
Issued
Sep 4, 2013
Abate by
Oct 22, 2013
Penalty
Initial $700 · Current $350 Reduced
29 CFR 1910.22(a)(3): To facilitate cleaning, every floor, working place, and passageway shall be kept free from protruding nails, splinters, holes, or loose boards.  a. Parking Lot, Loading Dock Area - On or about July 23, 2013, employees were required to walk through and across a passageway approximately 12'W X 15'L that had multiple potholes. The most severe depth of one of those potholes was four (4) inches deep. Thereby exposing employees to slip, trip, and fall hazard(s).
Recent events (2)
  • — I (O) $350
  • — Z (O) $700

1910.178 Q07

Other-than-serious 1 instance 1 exposed
Issued
Sep 4, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.178(q)(7): Industrial trucks shall be examined before being placed in service, and shall not be placed in service if the examination shows any condition adversely affecting the safety of the vehicle. Such examination shall be made at least daily. Where industrial trucks are used on a round-the-clock basis, they shall be examined after each shift. Defects when found shall be immediately reported and corrected.  a. On or about July 22, 2013, employees were required to operate a Powered Industrial Vehicle, (forklift) that was missing a back-up light (red lense) cover. Thereby exposing other employees working in the same area to struck by hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Safe AIR of Illinois, INC.'s full OSHA safety record →