WATERVILLE, ME —
OSHA Inspection: FAVREAU ELECTRIC, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of FAVREAU ELECTRIC, INC. in DRUMMOND & PIPER HALLS, WATERVILLE, ME 04901 (NAICS 238210). OSHA activity number 339230419.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FAVREAU ELECTRIC, INC.
- Site address
- DRUMMOND & PIPER HALLS
- City
- WATERVILLE
- State
- ME
- ZIP
- 04901
- Mailing
- P.O. BOX 598, BRUNSWICK, ME 04011
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 8
- Ownership type
- A
Citations
1 citation on file for this inspection.
1926.403 B02
- Issued
- Aug 8, 2013
- Abate by
- Aug 16, 2013
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Installation and use. Listed, labeled, or certified equipment shall be installed and used in accordance with instructions included in the listing, labeling, or certification. In the following instances nonmetallic-sheathed cable was not installed in accordance with the listing, labeling, and certification: a) Drummond Hall, Data Room - The spliced conductors were not completely enclosed with electrical tape, and the cable was not secured or supported within 12 inches of the splice. b) Drummond Hall, Storage Room - The spliced conductors were not completely enclosed with electrical tape, and the cable was not secured or supported within 12 inches of the splice. c) Piper Hall, Longue - The cable was not secured or supported within 12 inches of the splice.
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
More inspections at Favreau Electric, INC.
View Favreau Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in ME
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339230419.