OSHA Inspection: SOUTHSTAR, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SOUTHSTAR, LLC in 5801 KROGER DR., KELLER, TX 76248 (NAICS 493110). OSHA activity number 339232266.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Southstar, LLC — free Get an email when a new federal OSHA severe-injury report for Southstar, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
SOUTHSTAR, LLC
Site address
5801 KROGER DR.
City
KELLER
State
TX
ZIP
76248
Mailing
5801 KROGER DR., KELLER, TX 76248
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
411
Ownership type
A

6 citations on file for this inspection.

1910.22 A02

Serious Gravity 1 1 instance 15 exposed
Issued
Jan 17, 2014
Penalty
Initial $3,000 · Current $1,950 Reduced
29 CFR 1910.22(a)(2): Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition:      On or about July 23, 2013, the employer did not ensure that the workroom floor in receiving was maintained in a dry condition.  The employees were exposed to slip, trip and fall hazards.
Recent events (2)
  • — I (S) $1950
  • — Z (S) $3000

1910.23 C01

Serious Gravity 1 2 instances 10 exposed
Issued
Jan 17, 2014
Abate by
Feb 18, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent).    On or about July 23, 2013, the employer did not ensure the open sided floors were guarded with a standard guardrail or its equivalent, exposing employees to fall hazards of over 4 feet to the concrete below.    a)  Salvage, Door #5, west side, openings on both sides of the dock plates. b)  Salvage, Dock, west end.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.179 J02

Serious Gravity 10 1 instance 70 exposed
Issued
Jan 17, 2014
Abate by
Feb 18, 2014
Penalty
Initial $7,000 · Current $4,550 Reduced
29 CFR 1910.179(j)(2): The following items were not inspected for defects at intervals as defined in paragraph (j)(1)(ii) of this section or as specifically indicated, including observation during operation for any defects which might appear between regular inspections:      On or about July 23, 2013, and at times prior thereto, the employer did not perform monthly or daily crane inspections on the eight overhead cranes.     a)  3 Ton, Maintenance North  b)  3 Ton, Maintenance Middle  c)  3 Ton, Maintenance South Bridge  d)  5 Ton, Truck Shop, South  e)  5 Ton. Truck Shop, North  f)   5 Ton, West Battery  g)  3 Ton, East Battery  h)  1 Ton, Maintenance, East Wall
Recent events (2)
  • — I (S) $4550
  • — Z (S) $7000

1910.254 D09 III

Serious Gravity 1 1 instance 6 exposed
Issued
Jan 17, 2014
Abate by
Feb 18, 2014
Penalty
Initial $3,000 · Current $1,950 Reduced
29 CFR 1910.254(d)(9)(iii): Cables with damaged insulation or exposed bare conductors were not replaced.      On or about July 23 2013, the employer did not replace damaged welding cables that have damaged insulation resulting in exposed conductors on the Miller welding machine located in the Garage/Maintenance Building, exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $1950
  • — Z (S) $3000

1910.176 B

Deleted Repeat 1 instance 10 exposed
Issued
Jan 17, 2014
Abate by
Mar 11, 2014
Penalty
Initial $1,500 · Current $0 Reduced
29 CFR 1910.176(b): Storage of material created a hazard:  On or about July 23, 2013, the employer did not ensure the storage racks in the warehouse with damaged components were taken out of service, exposing employees to struck-by hazards.     The Southstar, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.176(b), which was contained in OSHA inspection number 716538, citation number 1, item number 1 and was affirmed as a final order on March 4, 2013, with respect to a workplace located at 5801 Kroger Dr., Keller, Texas 76248.
Recent events (3)
  • — F (R) $0
  • — C (R) $1500
  • — Z (R) $1500

1910.304 G05

Other-than-serious 1 instance 6 exposed
Issued
Jan 17, 2014
Penalty
Initial $1,500 · Current $950 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.    On or about July 23, 2013, the employer did not ensure the path to ground was permanent and continuous on the extension cord that was used to energizes the DeWalt Bench grinder.  Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (O) $950
  • — Z (O) $1500

View Southstar, LLC's full OSHA safety record →