OSHA Inspection: R. PALMIERI ELECTRIC

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of R. PALMIERI ELECTRIC in P.O.B. 490 939 HARDING, BUENA, NJ 08310 (NAICS 238210). OSHA activity number 339232597.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch R. Palmieri Electric for free Get an email when a new federal OSHA severe-injury report for R. Palmieri Electric is published. One employer, no account, unsubscribe in one click.
Site address
P.O.B. 490 939 HARDING
City
BUENA
State
NJ
ZIP
08310
Mailing
P.O.B. 490 939 HARDING, BUENA, NJ 08310
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
38
Ownership type
Private (A)

2 citations on file for this inspection.

1926.416 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 5, 2013
Penalty
Initial $4,900 · Current $3,430 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:     a)Third Floor: Laundry/Vending Area - A carpenter was exposed to a shock/electrocution hazard as energized power circuits [480 volts] were not de-energized and grounded or effectively guararded by insulation or other means. An employee was installing sheet rock/wallboard within several inches of an energized Alumna Flex/SEC cable that contained abraded sheathing. The employer did not adequately evaluate the installation and condition of the service entrance cable. This was observed on June 28, 2013.
Recent events (2)
  • · I (S) $3430
  • · Z (S) $4900

1926.403 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.403(b)(2): Installation and use. Listed, labeled, or certified equipment shall be installed and used in accordance with instructions included in the listing, labeling, or certification.    a) Third Floor Vending/Laundry Room  - The employer instructed their employee to install sheet rock/wallboard at the construction site. An employee worked adjacent to or within several inches of an energized conductor. The service entrance cable [SEC] was not properly installed and protected in accordance with the National Electrical Code,Article 338.10 (B)(4)(a). This was observed on June 28, 2013.