OSHA Inspection: R. PALMIERI ELECTRIC
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of R. PALMIERI ELECTRIC in P.O.B. 490 939 HARDING, BUENA, NJ 08310 (NAICS 238210). OSHA activity number 339232597.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- R. PALMIERI ELECTRIC
- Site address
- P.O.B. 490 939 HARDING
- City
- BUENA
- State
- NJ
- ZIP
- 08310
- Mailing
- P.O.B. 490 939 HARDING, BUENA, NJ 08310
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 38
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1926.416 A01
- Issued
- Dec 5, 2013
- Penalty
- Initial $4,900 · Current $3,430 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: a)Third Floor: Laundry/Vending Area - A carpenter was exposed to a shock/electrocution hazard as energized power circuits [480 volts] were not de-energized and grounded or effectively guararded by insulation or other means. An employee was installing sheet rock/wallboard within several inches of an energized Alumna Flex/SEC cable that contained abraded sheathing. The employer did not adequately evaluate the installation and condition of the service entrance cable. This was observed on June 28, 2013.
Recent events (2)
- · I (S) $3430
- · Z (S) $4900
1926.403 B02
- Issued
- Dec 5, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(b)(2): Installation and use. Listed, labeled, or certified equipment shall be installed and used in accordance with instructions included in the listing, labeling, or certification. a) Third Floor Vending/Laundry Room - The employer instructed their employee to install sheet rock/wallboard at the construction site. An employee worked adjacent to or within several inches of an energized conductor. The service entrance cable [SEC] was not properly installed and protected in accordance with the National Electrical Code,Article 338.10 (B)(4)(a). This was observed on June 28, 2013.