FARMINGTON, MO ·
OSHA Inspection: BASSETT DENTISTRY
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of BASSETT DENTISTRY in 19 SOUTH FRANKLIN, FARMINGTON, MO 63640 (NAICS 621210). OSHA activity number 339238537.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BASSETT DENTISTRY
- Site address
- 19 SOUTH FRANKLIN
- City
- FARMINGTON
- State
- MO
- ZIP
- 63640
- Mailing
- 19 SOUTH FRANKLIN STREET, FARMINGTON, MO 63640
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 621210
- Employees
- 6
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.304 G05
- Issued
- Sep 10, 2013
- Abate by
- Sep 27, 2013
- Penalty
- Initial $1,020 · Current $714 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. 1. In the staff lounge area, the General Electric refrigerator was not grounded. The duplex outlet the refrigerator is plugged into was not grounded. The hot and neutral wires on the outlet may be crossed. 2. In the staff lounge area, the General Electric toaster oven was not grounded. The circuit that the toaster oven is plugged into was not grounded. The hot and neutral wires on the outlet may be crossed. 3. In the staff lounge area, the General Electric microwave oven was not grounded. The circuit that the microwave oven is plugged into was not grounded. The hot and neutral wires on the outlet may be crossed.
Recent events (2)
- · I (S) $714
- · Z (S) $1020
1910.305 G01 IV A
- Issued
- Sep 10, 2013
- Abate by
- Sep 27, 2013
- Penalty
- Initial $1,020 · Current $714 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:(a)(LOCATION)(IDENTIFY EQUIPMENT AND CONDITION(S))(STATE HAZARD(S) TO EMPLOYEE(S)) 1. Inside of the compressor room, there was white romex wiring being used to energize the compressor. There was a switch box connected to the romex and the romex was plugged into a duplex outlet. The romex was connected to the compressor and extended to the duplex outlet. The compressor wire needs to be hard wired inside of conduit.
Recent events (2)
- · I (S) $714
- · Z (S) $1020
1910.1030 D02 VIII
- Issued
- Sep 10, 2013
- Abate by
- Sep 27, 2013
- Penalty
- Initial $1,020 · Current $714 Reduced
General-duty citation text
29 CFR 1910.1030(d)(2)(viii): Immediately or as soon as possible after use, contaminated reusable sharps shall be placed in appropriate containers until properly reprocessed. 1. Employees leave the operatories (procedure rooms) with needles and have to walk these needles to the x-ray room. The sharps containers are located under the counter in the film developing closet. All contaminated sharps have to be walked to that area from the operatories, increasing chance of injury to employees.
Recent events (2)
- · I (S) $714
- · Z (S) $1020
1910.305 B02
- Issued
- Sep 10, 2013
- Abate by
- Sep 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: In completed installations each outlet box shall have a cover, faceplate, or fixture canopy. 1. Inside of the employee lounge, on the wall near the General Electric refrigerator, there was a cover missing on the light switch. 2. Inside of the employee restroom, there was a cover missing from the junction box located on the ceiling. 3. Inside of the compressor room, there was a cover missing from the electrical box located on top of the compressor.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections in this industry (NAICS 621210)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339238537.