OSHA Inspection: GAS HOUSE PROPANE COMPANY, THE

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of GAS HOUSE PROPANE COMPANY, THE in 7125 KRICK RD, WALTON HILLS, OH 44146 (NAICS 454312). OSHA activity number 339241432.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch GAS House Propane Company, the for free Get an email when a new federal OSHA severe-injury report for GAS House Propane Company, the is published. One employer, no account, unsubscribe in one click.
Site address
7125 KRICK RD
City
WALTON HILLS
State
OH
ZIP
44146
Mailing
7125 KRICK RD, WALTON HILLS, OH 44146
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
454312
Employees
10
Ownership type
Private (A)

5 citations on file for this inspection.

1910.110 B13 II A

Serious Gravity 5 1 instance 8 exposed
Issued
Sep 9, 2013
Abate by
Sep 17, 2013
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.110(b)(13)(ii)(a): 29 CFR 1910.110(b)(13)(ii)(a) Liquid petroleum gas was piped into a building that was not used exclusively to house equipment for vaporization, pressure reduction, gas mixing, gas manufacturing, or distribution:     A workbench with tools used for maintenance was located in the cylinder recharging building.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.157 G01

Serious Gravity 5 1 instance 8 exposed
Issued
Sep 9, 2013
Abate by
Sep 27, 2013
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage firefighting:       Although portable fire extinguishers were available for employee use, neither initial, nor annual retraining was provided.       Note:  Employer may exercise one of the following options.       1.  Provide portable fire extinguishers as specified in 29 CFR1910.157(c)(1), meet the distribution requirements per 29 CFR1910.157(d) (75 feet to the nearest extinguisher for Class A fires and 50 feet to the nearest unit for Class B fires), and provide training and education for all employees in the use of such equipment and the hazards associated with incipient stage firefighting as required in 29 CFR 1910.157(g). The other sections of 29 CFR also apply.       2.  Provide extinguishers as specified in 29 CFR 1910.157(c)(1),designate certain employees to be the only employees authorized to use such equipment and require all other employees to immediately evacuate upon the sounding of the fire alarm, establish this in writing in an emergency action plan as outlined in 29 CFR1910.38(a) and train/educate designated employees per 1910.157(g).Utilizing this option exempts the employer from distribution requirements of 29 CFR 1910.157(d).      3.  Establish a written fire safety policy which requires the immediate and total evacuation of employees from the workplace upon the sounding of a fire alarm signal.  This policy shall include an emergency action plan and a fire prevention plan as specified in 29CFR 1910.38(a) and (b).  Utilizing this option exempts the employer from the requirements of 29 CFR 1910.157 to include the need for providing portable fire equipment unless a specific standard requires that a portable fire extinguisher be provided (such as those requirements in 29 CFR 1910.106/107 related to use/storage of flammable/combustible liquids).  If extinguishers are provided, but not intended for employee use, 29 CFR 1910.157(e) and (f) are still applicable (inspection, maintenance, and testing of equipment).
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.219 D01

Serious Gravity 1 1 instance 8 exposed
Issued
Sep 9, 2013
Penalty
Initial $1,200 · Current $720 Reduced
29 CFR 1910.219(d)(1):  Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):       Gas compressors located adjacent to the propane storage tanks had unguarded pulleys.
Recent events (2)
  • · I (S) $720
  • · Z (S) $1200

1910.1200 E01

Other-than-serious 1 instance 8 exposed
Issued
Sep 9, 2013
Abate by
Sep 27, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(e) (1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:    Employees work with paint which contains the hazardous chemicals toluene, xylene and ethyl benzene and Leak Detector which contains the hazardous chemicals ethylene glycol and propanol.  No written program was developed.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.1200 G08

Other-than-serious 1 instance 8 exposed
Issued
Sep 9, 2013
Abate by
Sep 27, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(g)(8):   The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work  shift to employees when they were in their work area:   No data sheets were available on the site for the  paint which contains the hazardous chemicals toluene, xylene and ethyl benzene and Leak Detector which contains the hazardous chemicals ethylene glycol and propanol.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339241432.