Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BME & SONS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BME & SONS, INC. in BLDG. B755 NAVAL MUNITIONS SITE, AGANA HEIGHTS, GU 96910 (NAICS 236220). OSHA activity number 339264251.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch BME & Sons, INC. — free Get an email when a new federal OSHA severe-injury report for BME & Sons, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
BME & SONS, INC.
Site address
BLDG. B755 NAVAL MUNITIONS SITE
City
AGANA HEIGHTS
State
GU
ZIP
96910
Mailing
PO BOX 24402 GMF, BARRIGADA, GU 96921
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
99
Ownership type
A

5 citations on file for this inspection.

1926.20 B02

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Oct 31, 2013
Abate by
Nov 1, 2013
Penalty
Initial $5,390 · Current $0 Reduced
29 CFR 1926.20(b)(2): The employer did not initiate and maintain programs which provided for frequent and regular inspections of the job site, materials and equipment to be made by a competent person(s):     BME & Sons Inc. - Naval Base Guam Munitions Site Building 775 - On or about August 8, 2013 and at times prior thereto an electrical safe work practices competent person was not provided by the employer to initiate and maintain a program for frequent and regular inspections of the jobsite to prevent employee electricians from working with and holding energized wire(s) to make electrical connections to  a new fixtures/ballast and ensuring electrical systems were de-energized and rendered inoperative in accordance with applicable construction electrical standards 1926.416 and 1926.417 to prevent shocks, burns and possible electrocution to the employee electricians. The Electrical Supervisor had locked and tagged the buildings main breaker with the switch in the "ON" position, circuit breakers for lighting in the "ON" position and the light switch to the room in the "ON" position.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5390

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 31, 2013
Abate by
Nov 1, 2013
Penalty
Initial $5,390 · Current $5,390
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:    BME & Sons Inc. - Naval Base Guam Munitions Site Building 775 - On or about August 8, 2013 and at times prior thereto employee electricians were not protected from wiring new lighting to live electrical circuits to prevent electric shock, burns and possible electrocution.  No operations were present at the structure requiring the electrical power to remain energized.
Recent events (2)
  • — I (S) $5390
  • — Z (S) $5390

1926.416 A03

Serious Gravity 10 2 instances 2 exposed
Issued
Oct 31, 2013
Abate by
Nov 1, 2013
Penalty
Initial $5,390 · Current $0 Reduced
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit.    BME & Sons Inc. - Naval Base Guam Munitions Site Building 775 - On or about August 8, 2013 and at times prior thereto BME & Sons Inc. did not ascertain by inquiry, direct observation, or by instruments, whether employee electricians wiring new lights to the exiting electrical branch circuit would contact any part of an energized electric power circuit prior to allowing employee electricians to come into contact with the energized circuits and exposure to shocks, burns and possible electrocution.  The main power box had been locked out with the switch in the on position, no circuit breaker locks were available and employee electricians did not have direct control over the light switches as other employee (painters) were also working in the rooms.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5390

1926.417 A

Serious Gravity 10 4 instances 2 exposed
Issued
Oct 31, 2013
Abate by
Nov 1, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged:   BME & Sons, Inc. - Naval Base Guam Munitions Site Bldg. 775 - On or about August 8, 2013 and at times prior thereto, the electrical competent person and/or the employee electrician did not did not tag the branch circuits 1,2, and 3 controlling the energized lights the employee electricians were wiring.  The competent person and/or employee electrician also did not place a tag on the light switch for the room where they were working on wiring new light fixtures.  The circuits were energized and electricians were working with the live branch wires exposing them to electrical shock, burns and possibly death.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 G08

Deleted Repeat 1 instance 2 exposed
Issued
Oct 31, 2013
Abate by
Nov 12, 2013
Penalty
Initial $1,540 · Current $0 Reduced
29 CFR 1910.1200(g)(8): The employer did not maintain, in the workplace, copies of the required material safety data sheets for each hazardous chemical, or ensure they were readily accessible during each work shift to employees at their work area(s).  (Construction Reference: 1926.59)  BME & Sons Inc. - Naval Base Guam Munitions site Bldg. B775 - On or about August 8, 2013 and at times prior thereto, the required material safety data sheet for the PPG Architectural Coatings Speed Hide Pro-EV Interior Enamel Latex Semi-gloss Paint was not present at the worksite.  Employee painters were using the product without access to the MSDS advising it contains titanium dioxide and kaolin which can cause respiratory tract and eye irritant,  The MSDS advises to avoid contact with the eyes, skin and clothing.     BME & Sons, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.1200(g)(8), which was contained in OSHA inspection number 488558, citation number 2, item number 1 and was affirmed as a final order on September 13, 2012, with respect to a workplace located at Naval Base Guam, Lockwood Housing, Unit 2251 Safford Rd., Santa Rita, Guam 96915.
Recent events (2)
  • — I (R) $0
  • — Z (R) $1540

View BME & Sons, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339264251.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.