NEWINGTON, CT —
OSHA Inspection: COMPONENT TECHNOLOGIES, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of COMPONENT TECHNOLOGIES, INC. in 68 HOLMES ROAD, NEWINGTON, CT 06111 (NAICS 332813). OSHA activity number 339276438.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COMPONENT TECHNOLOGIES, INC.
- Site address
- 68 HOLMES ROAD
- City
- NEWINGTON
- State
- CT
- ZIP
- 06111
- Mailing
- 68 HOLMES ROAD, NEWINGTON, CT 06111
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332813
- Employees
- 28
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.101 B
- Issued
- Jan 31, 2014
- Penalty
- Initial $2,310 · Current $1,115 Reduced
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: (a) Packaging Room: On or about August 9, 2013 a compressed gas cylinder, containing nitrogen, was not stored securely to prevent it from falling. (Ref. CGA P-1-1965 Section 3.3.1 referencing 2006 CGA P-1 Section 5.7.4.)
Recent events (2)
- — I (S) $1115
- — Z (S) $2310
1910.184 E01
- Issued
- Jan 31, 2014
- Abate by
- Mar 20, 2014
- Penalty
- Initial $4,620 · Current $1,845 Reduced
General-duty citation text
29 CFR 1910.184(e)(1): Alloy steel sling(s) did not have permanently affixed durable identification stating size, grade, rated capacity, and reach: (a) Plating lines: On or about August 12, 3013, an alloy steel sling used to dip baskets of parts to be electroplated was not labeled with its capacity.
Recent events (2)
- — I (S) $1845
- — Z (S) $4620
1910.305 A02 IX
- Issued
- Jan 31, 2014
- Penalty
- Initial $3,080 · Current $1,845 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard: (a) Maintenance: On or about August 12, 2013, a lamp mounted upon a utility work board, used for illumination was not protected from breakage by a guard or lampholder.
Recent events (2)
- — I (S) $1845
- — Z (S) $3080
1910.305 G01 IV A
- Issued
- Jan 31, 2014
- Abate by
- Mar 20, 2014
- Penalty
- Initial $4,620 · Current $1,845 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about August 12, 2013, flexible cord was used in lieu of permanent wiring: (a) Packaging Room - A PAC Vacuum Impulse Sealer was energized by a relocatable power tap. The power tap was overloaded and showed signs of damage
Recent events (2)
- — I (S) $1845
- — Z (S) $4620
1910.305 J02 I
- Issued
- Jan 31, 2014
- Penalty
- Initial $4,620 · Current $1,845 Reduced
General-duty citation text
29 CFR 1910.305(j)(2)(i): Receptacles were installed so as to require an energized attachment plug as its source of supply: (a) Finishing room: On, or about, August 22, 2013, a receptacle was energized through a cord and plug connection. The receptacle was used to energize an overhead light panel used for illumination.
Recent events (2)
- — I (S) $1845
- — Z (S) $4620
1910.1025 D02
- Issued
- Jan 31, 2014
- Abate by
- Jun 9, 2014
- Penalty
- Initial $2,310 · Current $2,310
1591
General-duty citation text
29 CFR 1910.1025(d)(2): An initial determination was not made to determine if any employee may be exposed to lead at or above the action level: (a) Plating Area: On or about August 22, 2013, the employer failed to complete an initial exposure determination for the following areas: 1. Employees that prepare a lead acetate solution for use in the nickel plating line 2. Employees that work on the nickel plating line.
Recent events (2)
- — I (S) $2310
- — Z (S) $2310
1910.1025 L01 II
- Issued
- Jan 31, 2014
- Abate by
- Jun 9, 2014
- Penalty
- Initial $0 · Current $0
1591
General-duty citation text
29 CFR 1910.1025(l)(1)(ii): The employer did not train each employee who is subject to exposure to lead at or above the action level, or for whom the possibility of skin or eye irritation exists, in accordance with the requirements of 29 CFR 1910.1025: (a) Plating Area: On or about August 22, 2013, the employer failed to train employees exposed to lead in the job tasks: 1. Preparation of a lead acetate solution for use in the nickel plating line 2. Employees that work on the nickel plating line.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1450 E01
- Issued
- Jan 31, 2014
- Abate by
- Jun 9, 2014
- Penalty
- Initial $3,850 · Current $3,850
General-duty citation text
29 CFR 1910.1450(e)(1): Where hazardous chemicals were used in the workplace, the employer did not develop and carry out the provisions of a written Chemical Hygiene Plan which was capable of protecting employees from health hazards associated with hazardous chemicals. (a) Lab: On or about August 9, 2013, the employer failed to develop a chemical hygiene plan that protects employees from health hazards associated with chemicals, such as, but not limited to, ethylenediaminetetraacetic acid (EDTA).
Recent events (2)
- — I (S) $3850
- — Z (S) $3850
1910.305 B01 II
- Issued
- Jan 31, 2014
- Penalty
- Initial $6,160 · Current $1,845 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Plating Area: On or about August 9, 2013, the 480/277 Volt, electrical panel "B" was missing a blank breaker cover, leaving a 2.5 inch wide by 1 inch high opening, exposing employees to electric shock hazards. Component Technologies, Inc. was previously cited for a substantially similar violation of this occupational safety and health standard, which was contained in OSHA inspection number 311783559, citation number 2, item number 3a and was affirmed as a final order on March 1, 2010, with respect to a workplace located in Newington, Connecticut.
Recent events (2)
- — I (R) $1845
- — Z (R) $6160
1910.151 C
- Issued
- Jan 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: (a) Plating area: On or about August 12, 2013, An eyewash station, plumbed to potable water, dispensed brownish, rust colored water when activated. The pH of the electroplating tanks ranged from 0.5 pH to 12.5 pH.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Component Technologies, INC.
View Component Technologies, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332813)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339276438.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.