NORTHAMPTON, PA —
OSHA Inspection: CAP GLASS, LLC
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of CAP GLASS, LLC in 799 SMITH LANE, NORTHAMPTON, PA 18067 (NAICS 423930). OSHA activity number 339277659.
Where did this inspection happen?
- Establishment
- CAP GLASS, LLC
- Site address
- 799 SMITH LANE
- City
- NORTHAMPTON
- State
- PA
- ZIP
- 18067
- Mailing
- 799 SMITH LANE, NORTHAMPTON, PA 18067
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423930
- Employees
- 18
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.37 A04
- Issued
- Penalty
- Initial $1200.00 · Current $720.00 Reduced
General-duty citation text
29 CFR 1910.37(a)(4): Safeguards designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting) must be in proper working order at all times. a) Production area South wall- On or about July 17, 2013, an emergency light would not illuminate when the test button was pushed, which would not provide the required illumination for employee egress in the event of emergency power loss. b) Production area East wall- On or about July 17, 2013, an emergency light would not illuminate when the test button was pushed, which would not provide the required illumination for employee to egress in the event of power loss.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.132 D01
- Issued
- Abate by
- Penalty
- Initial $1600.00 · Current $960.00 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards were present, or were likely to be present, which necessitated the use of personal protective equipment. 1) Facility wide - On or about July 17, 2013, employees were working in areas with electrical, eye, and hand hazards without the employer assessing the workplace to determine which personal protective equipment was necessary for proper employee protection.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.178 L01 II
- Issued
- Penalty
- Initial $1600.00 · Current $960.00 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(ii): The employer did not ensure that each operator had successfully completed the training required by paragraph (l), except as permitted by paragraph (l)(5), prior to permitting an employee to operate a forklift. a) Facility wide - On or about July 17, 2013, employees observed operating a forklift had not successfully completed the training necessary for safe operation prior to their initial usage.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.303 G02 I
- Issued
- Penalty
- Initial $2800.00 · Current $1680.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Electrical switch gear room - On or about July 17, 2013, employees were working in the area of multiple electrical control cabinets with exposed live parts energized to 277 Volts AC that were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.333 B02
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $1200.00 Reduced
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): a) Switch gear room - On or about July 17, 2013 employees were working on a 277 VAC motor control center with exposed, unprotected live parts that had not had the appropriate lockout devices or tagout devices affixed to isolate the electrical power and to prevent unexpected energization, start up or release of the stored energy as a control measure to prevent injury to the employees.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
More inspections in this industry (NAICS 423930)
DETROIT, MI—2026-07-15
STRONG STEEL PRODUCTS, LLC
OGDEN, UT—2026-07-10
TEAR A PART AUTO RECYCLING
GARNER, NC—2026-07-09
161490 - CAROLINA METAL RECYCLERS, LLC
JOPLIN, MO—2026-07-07
SERVICE RECYCLING - NORTH PLANT
HOLBROOK, NY—2026-07-01
ARROW SCRAP CORPORATION
More inspections in PA
PHILADELPHIA, PA—2026-07-16
URUS CONSTRUCTION CORPORATION
JEFFERSON HILLS, PA—2026-07-16
MARATHON PETROLEUM COMPANY ASPHALT TERMINAL
SMITHFIELD, PA—2026-07-16
CARLISLE CONSTRUCTION MATERIALS
PITTSBURGH, PA—2026-07-15
DREAM GREENER LAWN & LANDSCAPE
COCHRANTON, PA—2026-07-15
CRAWFORD COUNTY HARDWOODS, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339277659.